Table 64. Environmental requirements (continued)
Environment
Allowable
operating
Nonoperating
(system off)
Nonoperating
(storage)
Nonoperating
(shipping)
Temperature
5°C - 40°C (41°F -
104°F) at 0 - 950 m
(0 - 3117 ft)
Decrease maximum
system temperature
by 1°C for every 175
m (574 ft) above
950 m (3117 ft).
5°C - 28°C (41°F -
82°F) at 3050 m
(10000 ft)
5°C - 45°C (41°F -
113°F)
1°C - 60°C (33.8°F -
140.0°F)
-40°C to 60°C
(-40°F to 140°F)
Humidity range
Non-condensing:
-12.0°C (10.4°F)
dew point
Relative humidity
(RH): 8% - 85%
8% - 85% RH 5% to 80% RH 5% - 100% RH
Maximum dew point 24°C (75°F) 27°C (80.6°F) 29°C (84.2°F) 29°C (84.2°F)
Maximum altitude 3050 m (10000 ft) 3050 m (10000 ft) 3050 m (10000 ft) 10700 m (35105 ft)
Table 65. Noise emissions (Maximum conguration)
1
Acoustical characteristics Idling Operating
L
WAd
6.1 bels 6.1 bels
1. The noise emission level that is stated is the declared (upper limit) sound power level, in bels, for a random
sample of servers. All measurements are made in accordance with ISO 7779 and reported in conformance
with ISO 9296.
7063-CR1 Hardware Management Console specications
Hardware specications for model 7063-CR1 provide detailed information for your Hardware
Management Console (HMC), including dimensions, electrical, power, temperature, environmental
specications, and noise emissions.
The HMC controls managed systems, including the management of logical partitions and the use of
capacity on demand. Using service applications, the HMC communicates with managed systems to
detect, consolidate, and send information to IBM for analysis. The HMC provides service technicians with
diagnostic information for systems that can operate in a multiple-partitioned environment.
Use the following specications to plan for your HMC.
Table 66. Dimensions
Width Depth Height Weight
437 mm (17.2 in.) 705.3 mm (27.76 in.) 43.0 mm (1.7 in.) 14.5 kg (32 lb)
Site and hardware planning 65