CAUTION.
To avoid the possibility of injury during the installation, servicing or cleaning of
this appliance care should be taken when handling edges of sheet steel components.
All Gas Safe Registered Engineers carry a Gas Safe Register ID card, and have a registration number. Both should
be recorded in your Log Book. You can check your installer by calling Gas Safe Register direct on 0800 4085500
Introduction
The boilers are fully automatically controlled, oor
standing, fanned, super efcient condensing appliances.
Due to the very high efciency, condensate is produced from the
ue gases and this is drained to a suitable disposal point through
the plastic waste pipe at the bottom of the boiler. A condensate
'plume' will also often be visible at the ue terminal.
Safety
Current Gas Safety (Installation & Use)
Regulations or rules in force.
In your own interest, and that of safety, it is the law that this boiler
must be installed and maintained by a Gas Safe Registered
Engineer or in IE a competent person, in accordance with the
above regulations.
The appliance should be serviced at least once a year by a Gas
Safe Registered Engineer or in IE a competent person.
It is essential that the instructions in this booklet are strictly
followed, for safe and economical operation of the boiler.
Electricity Supply
The appliance must be earthed.
Supply 230 V - 50 Hz.
This appliance is intended to be connected to the supply via a
double-pole switch, having a 3mm contact separation in both
poles, serving only the boiler and system controls.
Important Notes
• This appliance must not be operated without
the casing correctly tted.
• Do not store objects around or on the boiler, and keep access
clear at all times.
• Do not obstruct ventilation ducts, grilles or openings in the
boiler room, room space or compartment that the appliance is
installed in, or the passage of combustion and ventilation to
the boiler.
• Do not turn off the boiler if it is to be left unattended in frosty
weather.
• If it is known or suspected that a fault exists on the boiler then
it MUST NOT BE USED until the fault has been corrected by a
Gas Safe Registered Engineer or in IE a competent person.
• Flammable materials must not be placed in close proximity to
the appliance. Materials giving off ammable vapours must not
be stored in the same room as the appliance.
In cases of repeated or continuous shutdown a Gas Safe
Registered Engineer or in IE a competent person should be called
to investigate and rectify the condition causing this and carry out
an operational test after each intervention on the device. Only the
manufacturers original parts should be used for replacement.
Minimum Clearances
Rear:
750mm or adequate space from the rear of the jacket to make the
ue connections, drain connection, ue and any safety or control
devices.
Left Side:
400mm.
Right Side:
450mm.
Front:
600mm for normal service and replacement of components.
However, it is noted that 1.2m is required in the event of heat
exchanger replacement.
Top:
300mm (clearance above boiler casing).
2
Natural Gas only
Destination Countries: GB, IE
EVOMOD 500 model shown
- Users