CHAPTER 1
CHAPTER 1 - PRE-INSTALLATION REQUIREMENTS
1.6. Combustion Air Contamination
If the EXALT combustion air inlet is located in an
area likely to cause or contain contamination, or if
products which could contaminate the air cannot
be removed, the combustion air must be repiped
and terminated at another location. Contaminated
combustion air will damage the unit and its burner
system, and can result in substantial property
damage, serious injury, or death.
Do not operate the EXALT if the combustion
air inlet is located near a laundry room or
pool facility. These areas will always contain
hazardous contaminants.
Pool, laundry, common household, and hobby
products often contain fluorine or chlorine
compounds. When these chemicals pass
through the burner and vent system, they can
form strong acids. These acids will corrode the
heat exchanger, burner components, and vent
system, causing serious damage and possible
flue gas spillage or water leakage into the
surrounding area.
Please read the information listed on the
right. If contaminating chemicals are located
near the area of the combustion air inlet, the
installer must pipe the combustion air inlet to
an area free of these chemicals.
Failure to comply with these instructions
will result in substantial property damage,
serious injury, or death.
If the combustion air is taken from the room,
an air grille must be installed to provide air for
combustion. The air grilles should be sized in
WARNING
DANGER
DANGER
accordance with ANSI Z223.1/ NFPA54 and/
or Natural Gas and Propane Installation Code
CAN/CSA B149.1.
The grilles providing air supply taken from
within the property should be clearly labeled
AIR SUPPLY, DO NOT COVER OR RESTRICT.
FAILURE TO PROVIDE ADEQUATE AIR FOR
COMBUSTION COULD RESULT IN SERIOUS
INJURY, OR DEATH.
Potential contaminating products
Spray cans containing chloro/uorocarbons
Permanent Wave Solutions
Chlorinated wax
Chlorine based swimming pool chemicals / cleaners
Calcium Chloride used for thawing ice
Sodium Chloride used for water softening
Refrigerant leaks
Paint or varnish removers
Hydrochloric acid / muriatic acid
Cements and glues
Antistatic fabric softeners used in clothes dryers
Chlorine-type bleaches, detergents, and clean-
ing solvents found in household laundry rooms
Adhesives used to fasten building products and
other similar products
Areas likely to contain these products
Dry cleaning / laundry areas and establishments
Beauty salons
Metal fabrication shops
Swimming pools and health spas
Refrigeration Repair shops
Photo processing plants
Auto body shops
Plastic manufacturing plants
Furniture renishing areas and establishments
New building construction
Remodeling areas
Garages with workshops
Table 2 - Approved AL29-4C® Stainless Steel Vent Adapters and Terminations
Description
SelKirk / Heatfab
Saf-T Vent EZ Seal or
Saf-T Vent SC
DuraVent
FasNSeal or CVS
Z-Flex U.S. Inc.
Z-Vent
3” Vent Adapter Not required Not required Not required
3” Roof & Side Wall Straight Termination 9392 300186 2SVSTPF03
3” Side Wall & 45° Elbow Termination 9311TERM 300130 & 300186 2SVSTEX0345
3” Side Wall Tee Termination 9390TEE 300311 2SVSTTF03

Table of Contents

Other manuals for IDEAL EXALT Solo 155

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEAL EXALT Solo 155 and is the answer not in the manual?

IDEAL EXALT Solo 155 Specifications

General IconGeneral
BrandIDEAL
ModelEXALT Solo 155
CategoryBoiler
LanguageEnglish

Related product manuals