Vent Termination
12" [30.5 cm]
(18” [45.7 cm] Canada)
Above the Highest
Anticipated Snow Level
24
CHAPTER 3
CHAPTER 3 - CATEGORY IV (INDOOR AIR) INSTALLATION OF VENT/AIR PIPING
3.1. Category IV - Vertical - Through the Roof
or Unused Chimney
The installation must conform to the
requirements of the authority having
jurisdiction or, in the absence of such
requirements, to the National Fuel Gas
Code, ANSI Z223.1/ NFPA 54, and/or Natural
Gas and Propane Installation Code, CAN/
CSA B149.1.
When using an inoperative chimney as a means
of a chase for the vent, the surrounding space
within the chimney cannot be used to draw
combustion air or vent another appliance.
A gas vent extending through a roof must not
terminate near an adjacent wall or below any
building extensions such as roof eaves, balconies
or decks.
Failure to comply with the required clearances
in this manual can result in substantial property
damage, serious injury, or death.
The information and diagrams outlining
the fittings and method of terminating the
vent/combustion air are directly related to
PVC/CPVC vent systems. When utilizing an
AL 29-4C
®
Stainless Steel or Polypropylene
vent system, there may be some variations.
Consult the appropriate vent manufacturer for
recommendations and clarifications.
NOTICE
WARNING
NOTICE
Fig. 15 - Category - IV - Vertical Termination of Vent Pipe
3.1.1 Determine Termination Location
Locate the vent and combustion air termination using
the following guidelines:
1. The total length of the vent piping must not exceed
the limits given in Table 1 on page 4.
2. The combustion air piping must terminate at the
boiler with a 90º elbow.
3. The vent piping must terminate vertically with
a coupling to accept the bird screen and must
be located 12” [30.5 cm] (18” [45.7 cm] in Canada)
above the highest anticipated snow level as shown
in Fig. 15 on page 24 below.
4. The following should be considered when
determining the location of the vent termination:
a. Locate the vent termination where ue vapors
will not damage surrounding shrubs, plants, air
conditioning equipment or be objectionable to
the homeowner.
b. The ue products will form a noticeable plume
of water vapor as they condense in colder air.
Avoid terminating the vent in areas where the
plume could obstruct window views.
c. Prevailing winds could cause freezing of ue
gas condensation and a buildup of water / ice
on surrounding plants or building surfaces.
d. Avoid locations where prevailing winds could
aect the performance of the boiler or cause
recirculation of the ue gases, such as inside
corners of buildings, near adjacent buildings,
vertical surfaces, window wells, stairwells,
alcoves, courtyards, or other recessed areas.
e. Do not terminate the vent above doors or
windows, ue condensate could freeze causing
ice formations.
f. Locate the vent termination to prevent possible
condensate damage to exterior nishes.
g. Avoid locations of possible accidental contact
of ue vapors with people or pets.
5. The vent termination must also maintain the
following clearances; as shown in Fig. 16 on page
25.
a. At least 3 feet [0.9 m] from adjacent walls
b. At least 3 feet [0.9 m] below roof overhangs
c. At least 7 feet [2.1 m] above any public walkways

Table of Contents

Other manuals for IDEAL EXALT Solo 199

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEAL EXALT Solo 199 and is the answer not in the manual?

IDEAL EXALT Solo 199 Specifications

General IconGeneral
BrandIDEAL
ModelEXALT Solo 199
CategoryBoiler
LanguageEnglish

Related product manuals