5 Troubleshooting
- 33 -
5.3 System Error Code D8062
Error Code Content
D8062
Communication error in control panel or program
connection port
6200-6279 serial communication and con󶍾guration error codes
6201 Receiving timeout
6202 CAN transmitting busy
6203 CAN receiving busy
6204 Data format incorrect
6205 Instruction incorrect
6206 Communication element exceeding range
6207 Communication port exceeding range or not existing
6208-6279 Reserved
6280-6299 CAN communication con󶍾guration error code
16200-16219 Ethernet con󶍾guration error code
16200 Reserved
16201
Ethernet con󶍾guration: function codes not
supported
16202
Ethernet con󶍾guration: register start address
incorrect or start address plus number of registers
incorrect
16203 Ethernet con󶍾guration: number of registers too large
16204
Ethernet con󶍾guration: reading/writing register
failed.
16205 Ethernet con󶍾guration: ACK signal
16206 Ethernet con󶍾guration: slave busy
16207 Ethernet con󶍾guration: station number incorrect
16208 Ethernet con󶍾guration: memory check error
16209 Reserved
16210 Ethernet con󶍾guration: gateway path error