EasyManuals Logo
Home>Interlogix>Control Unit>TruPortal TP-ADD-2D Series

Interlogix TruPortal TP-ADD-2D Series User Manual

Interlogix TruPortal TP-ADD-2D Series
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #3 background imageLoading...
Page #3 background image
TruPortal Dual Door Interface Quick Reference 3 P/N 460802991B 26JAN12 en-US
Door Contact Detail and Request to Exit
Final Steps
1. Ensure the reader voltage jumpers match your specific readers.
2. Apply power to the unit and listen for the relays to click, verifying
LED indicators for correct board operation.
3. When finished, ensure all wires are clear and secure of the cover
before closing.
Specifications
The TP-ADD-2D is for use in low voltage, Class 2 circuits only. These
specifications are subject to change without notice.
Incoming power ratings: 12 VDC, 300 mA max
Outputs
- Four outputs: Relay type
- Door strike: 24 VDC/1A
- Aux: 24 VDC/0.1A
Inputs
- Eight (8) unsupervised/supervised, standard EOL, 1k/1k ohm,
1% 1/4 watt
- One (1) unsupervised, dedicated for cabinet tamper
Reader interface
- Four interfaces
- Reader power (jumper selectable): 12 VDC +
10% regulated,
125 mA maximum each reader or 5 VDC +
10% regulated,
600 mA maximum each reader
Communication: SNAPP bus
Cable requirements
- Power: 18 AWG (1.024 mm / 0.823 mm
2
), 1 stranded
- Reader data: 6 conductors, 18 AWG (1.024 mm / 0.823 mm
2
),
500 feet (150 m) maximum
- SNAPP bus (RS-485): 22 AWG (0.644 mm / 0.326 mm
2
),
100 ohm impedance, twisted pair with shield, 4000 feet
(1219 m) maximum
Mechanical
- Dimensions: 5.75 x 4.25 x 1 in. (146 x 108 x 25 mm)
Environmental
- Temperature: 32 to 120° F (0 to 49° C )
- Humidity: 5 to 85% RHNC at 77° F (25° C)
- BTU Output: 12.3 BTU/hour
Certifications
-CE marking
- RoHS compliant
-WEEE
Callout Description Callout Description
1 Typical door contact
circuit (dual EOL)
4 Install resistors
close to the door
contact
2 Door contact input 5 Door contact (must
match/follow the
door state)
3 COM/shared
1 kΩ
1 kΩ
5
4
1
3
2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Interlogix TruPortal TP-ADD-2D Series and is the answer not in the manual?

Interlogix TruPortal TP-ADD-2D Series Specifications

General IconGeneral
BrandInterlogix
ModelTruPortal TP-ADD-2D Series
CategoryControl Unit
LanguageEnglish