EasyManuals Logo
Home>INVT>DC Drives>CHV100 Series

INVT CHV100 Series User Manual

INVT CHV100 Series
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #90 background imageLoading...
Page #90 background image
Detailed Function Description
82
Function
Code
Name Description
Setting
Range
Factory
Setting
P8.16 Auto reset times 0~3
0~3 0
P8.17 Fault relay action
0: Disabled
1: Enabled
0~1 0
P8.18 Reset interval 0.1~100.0s
0.1~100.0 1.0s
Auto reset function can reset the fault in preset times and interval. When P8.16 is set to
be 0, it means “auto reset” is disabled and the protective device will be activated in case
of fault.
P8.17 defines if fault relay active or not during auto reset. If continuous production
without interruption is needed, please set P8.17=0.
Notice:
z The fault such as OUT 1, OUT 2, OUT 3, OH1 and OH2 cannot be reset
automatically.
z If fault has not occurred for ten minutes after the fault is reset, inverter will
automatically clear the previous times of auto reset.
Function
Code
Name Description Setting Range
Factory
Setting
P8.19 Preset length 1~65535 1~65535 1000
P8.20 Actual length 0~65535 0~65535 0
P8.21
Number of pulse
per cycle
0.1~6553.5 0.1~6553.5 100.0
These parameters are mainly used for fixed-length control.
The length is calculated by input pulse signal. If input pulse frequency is high, it is
required to use HDI1 or HDI2 input (P5.35 or P5.36 = 2)
Actual length (P8.20) = Accumulated input pulse number / Number of pulse per cycle
(P8.21).
When the value of P8.20 exceeds the value of P8.19, if multifunctional output terminal is
set to be 11 (Length reached), ON signal will be output.
Function
Code
Name Description
Setting
Range
Factory
Setting
P8.22 Preset count value 1~65535 1~65535 1000
P8.23 Specified count value 1~65535 1~65535 1000