FCP-NA-701, FCP-PA-701
24-11482-00006 Rev. —
5
Prole # Remote
sensor
Pipe
sensor
System
type
2-pipe
FCU
with
aux
heat
Available modes:
1: heat only
2: cool only
3: heat and cool
with Auto
4: heat and cool
without Auto
HP
valve
type
Remote
sensor
location:
0: in room
1: in duct
Pipe state -
calendar
Pipe
state:
0: heat
1: cool
Number
of fan
speeds
1 Yes Yes 2-pipe FCU Yes 3 - 0 O󰀨 - 3
2 Yes Yes 2-pipe FCU Yes 3 - 1 O󰀨 - 3
3 Yes Yes 2-pipe FCU No 4 - 0 O󰀨 - 3
4 Yes Yes 2-pipe FCU No 4 - 1 O󰀨 - 3
5 Yes No 2-pipe FCU Yes 3 - 0 On - 3
6 Yes No 2-pipe FCU Yes 3 - 1 On - 3
7 Yes No 2-pipe FCU No 4 - 0 On - 3
8 Yes No 2-pipe FCU No 4 - 1 On - 3
9 No Ye s 2-pipe FCU Ye s 3 - - O󰀨 - 3
10 No Ye s 2-pipe FCU No 4 - - O󰀨 - 3
11 No No 2-pipe FCU Ye s 3 - - On - 3
12 No No 2-pipe FCU No 4 - - On - 3
13 No No 2-pipe FCU No 4 - - O󰀨 0 3
14 No No 2-pipe FCU No 4 - - O󰀨 1 3
15 Yes No 4-pipe FCU - 3 - 0 - - 3
16 Yes No 4-pipe FCU - 3 - 1 - - 3
17 No No 4-pipe FCU - 3 - - - - 3
18 No No HP - 3 O - - - 2
19 No No HP - 3 B - - - 2
20 No No H-C - 3 - - - - 2
Table 2: Preset conguration proles
Button combinations
The following table describes the button combinations that you can use to access menus or functions. The table also indicates the
modes in which these button combinations are applicable.
Menu or function Applicable in mode Button combination
Advance setting menu OFF mode Mode + Fan for 5 seconds
Access programming menu OFF mode, when programming
is enabled in advanced settings
Mode + Up for 5 seconds
Pipe State (Heat/Cool) Selection OFF mode and system type =
2-pipe FC
Fan + Up for 5 seconds
Ex-Factory Reset OFF mode Mode + Fan + Up for 5 seconds
Toggle Keypad lock/unlock HEAT and COOL mode Mode + Up + Down for 10 seconds
Toggle EMER HEAT HEAT mode Mode + Down for 5 seconds
Enable/Disable unoccupied mode manually HEAT and COOL mode Mode for 5 seconds
Table 3: Button combinations

Questions and Answers: