P/N 24-85784-119 Rev. - Issue Date 11 2012
T5000-E English
Instructions
• On/off: press to turn on, press again to turn off, close the fan and valve.
• Setting temperature: Press either or buttons to increase or decrease the setpoint by 0.5 °C.
• Mode selection: press to change the working mode, cooling, heating, ventilating (no heat mode for T5200-TC-9JS0)
• Fan speed selection: press to choose the speed (hi), (med), (low), (auto).
Under “AUTO” mode, the fan-speed will be changed automatically. Auto LOW-speed when the difference between room
temperature and set-point exceed 1 °C, Auto MED-speed when exceed 2 °C, Auto HI-speed when exceed 3 °C.
• Valve Control: under cool (heat) mode, the valve will be open while the difference between room temperature and setpoint
exceed 1 °C; while the room temperature reaches setpoint, the valve is closed with the fan still running.
Time-On and Time-Off Operation
• Hold down the button for 3 seconds will enter the Timer On-Off setting. When the , and appear, press and
keys to set the duration of the time delay for automatic switch ON.
Press button again, , and appear, press and keys to set the duration of the time delay for automatic switch
OFF. Set time duration to , to cancel the setting.
After one cycle for Time-on and Time-off the setting will be automatically canceled.
Lock function
• Lock function: The thermostat will be locked automatically after 0 seconds under the lock function. Hold down the fan key 5
seconds to unlock.
Unoccupied energy-saving mode (T5200-TB-9JS0)
• Unoccupied energy-saving mode (by entrance card): While entrance card is pulled out, the temperature automatically set to
26 °C, fan is on LO-speed if the thermostat is in cool mode; the temperature set to 18 °C, fan is on LO-speed if in heat mode.
Low Temperature protection setting
• On power Off status and when room temperature is lower than 5 °C, heat function will be automatically switched on, appears,
the fan is set to HI-speed and the valve (heat valve for T5200-TF-9JS0) is opened. When the room temperature reaches 7 °C, the
setting will be automatically canceled.
• On power Off status, press and keep 5 seconds, display or , press , to adjust the parameter. means
cancelling low temperature protection, means the protection function is on. Factory setting is .
Temperature setting
If customers hope the displayed temperature higher or lower than the real temperature, operate as follows:
• On power off status, press both and , keep 5 seconds, display (no working mode display), press or adjust
the temperature, auto-confirmed after 6 seconds.
Alarm
• When the sensor is in fault, thermostat will close the fan and valve, display , and .
: Sensor short cut alarm
: Sensor circuit breaker alarm
Display , temperature > 55 °C; display , temperature < 0 °C
Functional Code Setting Table (only when Thermostat is OFF)
• Enable the setting table: hold down the and for 5 seconds, 01 and code appeare, after which press button to select
code, use and buttons to adjust the value.
Code
T5200-
TB-9JS0
T5200-
TF-9JS0
Parameter Name Defaulf Function
01
°F / °C C F: Fahrenheit Degree (°F)
C: Celsius Degree (°C)
02
Upper limit of set temp 35.0 °C Setting Range 2 ~ 49.5 °C
03
Lower limit of set temp 5.0 °C Setting Range 0 ~ 47.5 °C
04
Keypad lockout 00 00: No lock
01: Lock all keys
02: Lock ON/OFF key
03: Lock the keys except ON/OFF key
05
Screen Display 00 00: Display room temp
01: Display set temp
06
--- Auto or Manual Mode Switch 00 00: Manual Mode
01: Auto Mode
06
--- Key Card Status 01 00: S1, S2 Short Connection indicates key card is
inserted;
Disconnection indicates key card is pulled out
01: S1, S2 Disconnection indicates key card is
inserted;
Short Connection indicates key card is pulled out
07
--- Cooling Temp when key card is pulled out 26.0 °C Setting Range 22 ~ 32 °C
08
--- Heating Temp when key card is pulled out 18.0 °C Setting Range 10 ~ 21 °C