TP-6109 6/03 5Section 1 Specifications
1.4 Remote Annunciator Kit
A remote annunciator provides convenient monitoring
of the generator set’s condition from a remote location.
See Figure 1-3. The remote annunciator includes an
alarm horn, alarm silence switch, lamp test, and the
same lamp indicators (except air damper and auxiliary
prealarm) as the microprocessor controller, plus the
following lamps:
Line Power lamp illuminates to indicate that the
commercial utility is the power source.
Generator Power lamp illuminates to indicate that the
generator set is the power source.
Remote Annunciator
14-Relay Dry Contact Box
A-293983
A-258782
NO C CNO CNO CNO CNO CNO CNO CNO CNO CNO CNO CNO CNO CNO
K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 K14
INPUT
CONTACT RATINGS: 10A @120VAC RES. LOAD
.01A @28VDC MIN.
10A @28VDC MAX.
PCB ASSY A-- 320639
LOT NO.
42A 2 K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K13K14K12
10 AMP
42B
FBA--1
P
Figure 1-3 Remote Annunciator with 14-Relay Dry
Contact Box
1.5 Safeguard Breaker
The safeguard breaker senses output current on each
generator phase and shuts off the AC voltage regulator if
a sustained overload or short circuit occurs. It is not a
line circuit breaker and does not disconnect the
generator set from the load. See Figure 1-4.
X-796
Figure 1-4 Safeguard Breaker
1.6 Line Circuit Breaker
The line circuit breaker interrupts generator output if an
overload or short circuit occurs. Use the line circuit
breaker to manually disconnect the generator set from
the load during generator set service. See Figure 1-5.
TP-5352-1
Figure 1-5 Line Circuit Breaker
1.7 Run Relay Kit
The run relay kit includes three sets of contacts that
energize only during generator set operation. The run
relay kit can control air intake louvers, radiator louvers,
alarms, and other signaling devices. See Figure 1-6.
273705
Figure 1-6 Run Relay Kit