TP-6905 7/1838 Section 3 RDC2 Controller Operation
3.10 Generator Metering Menu
The generator metering menu displays the generator
voltage and frequency. See Figure 3-10.
The voltage calibration mode can be entered from the
generator metering menu.
Voltage Calibration
Hazardous voltage.
Will cause severe injury or death.
This equipment must be installed and
serviced by qualified electrical
personnel.
DANGER
The voltage calibration mode can be entered from the
Generator Metering menu. Contact a Kohler-authorized
distributor/dealer for service.
The Reset Calibration menu allows you to set the
voltage reading back to the original value after
calibration, if necessary. See Figure 3-10.
Volts L1--L2:
240 V
Volts L2--L3:
240 V
Volts L3--L1:
240 V
Generator ---->
Metering
Reset
Calibration
<---- Return
Reset
Calib? No
Volts:
240 V
Three-phase
Single-phase
tp6810
Reset
Calib? Yes
Frequency:
60.0 Hz
Frequency:
60.0 Hz
Figure 3-10 Generator Metering Menu

Table of Contents

Other manuals for Kohler RDC2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler RDC2 and is the answer not in the manual?

Kohler RDC2 Specifications

General IconGeneral
BrandKohler
ModelRDC2
CategoryPortable Generator
LanguageEnglish

Related product manuals