EasyManuals Logo
Home>Lennox>Heat Pump>14HPX-036-230-17

Lennox 14HPX-036-230-17 User Manual

Lennox 14HPX-036-230-17
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
Page 12
NOTES:
Service clearance of 30 in. (762 mm) must be maintained on one
of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in. (914 mm)
Clearance to one of the remaining two sides may be 12 in. (305
mm) and the final side may be 6 in. (152 mm).
A clearance of 24 in. must be maintained between two units.
48 in. (1219 mm) clearance required on top of unit.
See
NOTES
See NOTES
See NOTES
See
NOTES
CONTROL
BOX
NOTICE: Specific applications may require adjustment of the listed installation clearances to provide protection for
the unit from physical damage or to avoid conditions which limit operating efficiency. (Example: Clearances may
have to be increased to prevent snow or ice from falling on the top of the unit. Additional clearances may also be
required to prevent air recirculation when the unit is installed under a deck or in another tight space.)
Figure 4. Installation Clearances
INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE TOLERANCE
OF 2 DEGREES (OR 2 INCHES PER 5 FEET [50 MM PER 1.5 M]) AWAY
FROM BUILDING STRUCTURE.
DETAIL A
DETAIL B
INSTALL UNIT AWAY
FROM WINDOWS
TWO 90 ELBOWS INSTALLED IN LINE SET
WILL REDUCE LINE SET VIBRATION
GROUND LEVEL
MOUNTING
SLAB
BUILDING
STRUCTURE
DISCHARGE AIR
Figure 5. Placement, and Slab Mounting
Unit Placement
See Unit Dimensions on page 4 for sizing mounting slab,
platforms or supports. Refer to figure 4 for mandatory
installation clearance requirements.
CAUTION
In order to avoid injury, take proper precaution when lifting
heavy objects.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
Some localities are adopting sound ordinances based
on the unit's sound level registered from the adjacent
property, not from the installation property. Install the
unit as far as possible from the property line.
When possible, do not install the unit directly outside a
window. Glass has a very high level of sound
transmission. For proper placement of unit in relation to
a window see the provided illustration in figure 5, detail
A.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox 14HPX-036-230-17 and is the answer not in the manual?

Lennox 14HPX-036-230-17 Specifications

General IconGeneral
BrandLennox
Model14HPX-036-230-17
CategoryHeat Pump
LanguageEnglish

Related product manuals