EasyManuals Logo
Home>Lennox>Heat Pump>16HPX Series

Lennox 16HPX Series User Manual

Lennox 16HPX Series
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #4 background imageLoading...
Page #4 background image
Page 4
Specications
General
Data
Model No. 16HPX-024 16HPX-036 16HPX-048 16HPX-060
Nominal Tonnage 2345
1
Sound Rating Number (dB) 74 82 81 80
Connections
(sweat)
Liquid line (o.d.) - in. 3/83/8 3/83/8
Vapor line (o.d.) - in. 3/47/8 7/8 1-1/8
² Refrigerant R-410A charge furnished 7 lbs. 14 oz.10 lbs. 8 oz.9 lbs. 9 oz.11 lbs. 8 oz.
Outdoor
Coil
Net face area - sq. ft. Outer coil 15.11 24.5024.94 29.09
Inner coil 14.50 23.6324.19 28.16
Tube diameter - in. 5/165/165/165/16
No. of rows 2222
Fins per inch 22 22 22 22
Outdoor
Fan
Diameter - in. 18 22 26 26
No. of blades 3433
Motor hp 1/101/4 1/31/3
Cfm - 1st stage 22324500 4500 3690
2nd stage - - -- - -- - -4250
Rpm - 1st stage 1075825 825700
2nd stage - - -- - -- - -820
Watts - 1st stage
145 290290 130
2nd stage - - -- - -- - -195
Shipping Data - lbs. 1 pkg. 173 233256 284
ELECTRICAL DATA
Line voltage data - 60hz
5
230V-1ph
5
230V-1ph
5
230V-1ph
5
230V-1ph
3
Maximum overcurrent protection (amps) 25 35 45 60
4
Minimum circuit ampacity 15.322.528.336.7
Compressor Rated load amps 11.7 16.6 21.2 27.1
Locked rotor amps 58 83 104153
Power factor 0.980.990.990.99
Outdoor Coil Fan Motor Full load amps 0.71.7 1.82.8
CONTROLS - ORDER SEPARATELY
iComfort
®
M30 Smart Wi-Fi Thermostat 15Z69 ••••
Remote Outdoor Temperature Sensor X2658 ••••
OPTIONAL ACCESSORIES - ORDER SEPARATELY
Blower Relay Kit
(for constant torque gas furnaces)
85W66 ••••
Compressor Hard Start Kit - Required
in applications with less than 230V
63W22
10J42 ••
63W24
Compressor Sound Cover 27W55 ••
27W56 ••
Freezestat 3/8 in. tubing 93G35 ••••
5/8 in. tubing 50A93 ••••
Indoor Blower Speed Relay Kit 40K58 ••••
58M81 ••••
6
Low Ambient Kit 54M89 •••
68M04
Mild Weather Kit 11B97 ••••
Monitor Kit - Service Light 76F53 ••••
Outdoor
Thermostat Kit
Thermostat 10Z23 ••••
Mounting Box 31461 ••••
Refrigerant Line
Sets
L15-41-20 L15-41-40
L15-41-30 L15-41-50
L15-65-30 L15-65-40
L15-65-50
••
Field Fabricate
94J45 ••••
NOTE - Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Sound Rating Number in accordance with test conditions included in AHRI Standard 270.
2
additional refrigerant charge required.
3
HACR type breaker or fuse.
4
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
5
Hard start kit is required in applications where the supply voltage is less than 230V.
6
Freezestat is recommended with Low Ambient Kit.