# 48306B006 Page 7
Figure 8
Refrigerant Line Sets: Installing Vertical Runs (new construction shown)
Outside Wall
Wood Block
Between Studs
IMPORTANT: Refrigerant
lines must not contact wall.
Vapor Line
Liquid Line
Wire Tie
Inside Wall
Strap
Sleeve
Wire Tie
Wire Tie
Strap
Wood Block
Sleeve
Vapor Line Wrapped
with Armaflex
Liquid Line
Caulk
PVC Pipe
Fiberglass
Insulation
Outside Wall
IMPORTANT:
Refrigerant
lines must not
contact structure.
NOTE: Similar installation practices
should be used if line set is to be
installed on exterior of outside wall.
Fixed Orifice Data
Table 3
ledoM
traP
rebmuN
llirD
eziS
81-31PHS280-484001750.
42-31PHS2 11-484001 160.
03-31PHS212-484001270.
63-31PHS2 32-484001 470.
24-31PHS233-484001680.
84-31PHS2 53-484001 880.
06-31PHS273-484001090.
Metering Device Installation
Figure 9
If installing an expansion valve on an indoor coil that
previously used a fixed orifice, remove orifice before
installing valve.