507266-05Page 48 of 58 Issue 1933
Blower Performance
95G2UH045BV12
Temp. Rise Speed Adjustment
Heating CFM @ 0 - 0.8” w.c.
Setting D Setting C Setting B Setting A
High Fire
35-65
+ 745 875 990 1005
Normal 685 765 895 910
- 610 695 785 810
Low Fire
20-50
+ 685 765 895 910
Normal 620 705 800 820
- 545 625 715 725
Cooling Stage Cooling CFM @ 0 - 0.8” w.c.
2nd Stage
+ 905 1075 1210 1370
Normal 815 980 1120 1255
- 720 885 1020 1135
1st Stage
+ 595 760 865 980
Normal 540 660 785 890
- 485 600 695 790
95G2UH070BV12
Temp. Rise Speed Adjustment
Heating CFM @ 0 - 0.8” w.c.
Setting D Setting C Setting B Setting A
High Fire
50-80
+ 965 1060 1130 1255
Normal 880 960 990 1140
- 810 840 890 1030
Low Fire
25-55
+ 940 990 1070 1195
Normal 830 895 965 1100
- 755 825 840 975
Cooling Stage Cooling CFM @ 0 - 0.8” w.c.
2nd Stage
+ 860 1060 1215 1365
Normal 810 960 1130 1265
- 705 840 1005 1140
1st Stage
+ 600 740 840 970
Normal 555 665 770 855
- 500 600 680 790