• 26 • BALTIC-IOM-0412-E / Installation manual
THERMODYNAMIC HEAT RECOVERY - CONTROL MANUAL
1. CONFIGURATION
Con guration of CLIMATIC™ 60 with the DS60 in expert mode for TRMO (with a modulating exhaust fan):
3813 RECOV. = Comp. for TRMO
3815 EXHAUST = Modulate for both ERVF & EBHO
3816 KIT
3817 Motor to be checked function of your need
3818 Fan
2. USE
Protection:
Operating envelop Protection: compressor stopped during 6 minutes.
- 328: min HP = 20.5°C condensation;
- 329: max HP = 62°C condensation;
- 319: min LP = between -24.5°C and 1.6°C (function of the condensation temperature) during 5 min => freezing or air ow on
evaporator issue;
- 327: max LP = 26°C.
- 317: limit LP -27°C during 120 sec => frigori c failure (lack of refrigerant /closed components)
Anti freezing Protection consist in defrosting the exhaust coil in heating mode with the extract air.
Control
• No speci c parameters have to be set for TRMO control.
• Operation:
- TRMO runs if there is heating or cooling needs;
- above 50% fresh air, TRMO compressor has priority to start;
- under 15°C return or under 20% fresh air, TRMO compressor is not authorized to start.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox BAC 052 DNM 3M and is the answer not in the manual?

Lennox BAC 052 DNM 3M Specifications

General IconGeneral
BrandLennox
ModelBAC 052 DNM 3M
CategoryAir Conditioner
LanguageEnglish

Related product manuals