• 40 • BALTIC-IOM-0412-E / Service manual
eDrive™ VENTILATION
eDrive™ fan inverter con guration
eDrive™ Inverter con guration is prepared in the factory to communicate with CAREL & to be con gured speci cally for the customer
machine.
eDrive™ Fan inverter parameters are con gured via the CLIMATIC™ 60 unit con guration (See CLIMATIC™ Section).
This con guration is selecting the proper parameters to run eDrive™ in its operating range depending on fan type & motor size.
If ever, the Inverter loose fan control (No Fan or Wrong fan speed & Compressor or Heating stay on), one may check the Inverter
con guration as below:
“0.0” will be displayed in this case on the Inverter instead of the regular “0” or “xxx” rpm
Switch to unlock mode:
F700 = 0
F732 = 0
On Inverter, set the TYP parameter to 3 value. (reinitialize the Inverter to the default values) then con gure the following setpoints:
CMOD=2
FMOD=4
F800=1
F801=0
F802=11
F803=0
Then switch OFF the whole machine & then switch ON.
Then the CLIMATIC™ is going to send all the proper machine con guration to Inverter (motor size, fan type, Imax, safety parameters) .

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox BAC 052 DNM 3M and is the answer not in the manual?

Lennox BAC 052 DNM 3M Specifications

General IconGeneral
BrandLennox
ModelBAC 052 DNM 3M
CategoryAir Conditioner
LanguageEnglish

Related product manuals