• 7 •
A
1150
(1)
1650
(1)
2150
(1)
BALTIC-IOM-0412-E / Installation manual
LIFTING THE UNITS
Minimum clearance around the unit installation
Figure below show the required clearances and service access around the unit.
Fork lifting the unit
Do not lift the unit by the side (coil end side or drain pan outlet side). This will damage the unit.
Lift the unit on the long side using a forklift with dimensions according to the gure below.
Do not remove the unit plastic cover while lifting.
IMPORTANT note for unit clearances
Ensure the fresh air inlet does not face prevailing wind direction.
If machine is including gas burner, minimum clearance around the unit must be at least 8 m to allow a proper gas ue dilution. If
not possible, the fresh air intake must be ducted at least 8 m away from the gas burner exhaust.
In case of extraction option, it is recommended to duct fresh air intake.
Drain pan clearance (A)
C Box
D Box
E Box
Plastic cover must not be removed before
lifting
NO
DO NOT LIFT THIS SIDE

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox BAC 057 DNM 3M and is the answer not in the manual?

Lennox BAC 057 DNM 3M Specifications

General IconGeneral
BrandLennox
ModelBAC 057 DNM 3M
CategoryAir Conditioner
LanguageEnglish

Related product manuals