• 30 •
1/2 2/3 1/3
N°1 N°2
3410: 3411: 3412:
BALTIC-IOM-0412-E / Service manual
COMMISSIONING RECORD SHEET
Site details Controller
Site Model
Unit Ref Serial No
Installer Refrigerant
(1) ROOF INSTALLATION
Suffi cient Access OK Condensate drain fi tted Roofcurb
Yes No Yes No OK Not OK
(2) CONNECTIONS CHECK
Phase check
Voltage between Phases
Yes No
(4) SUPPLY BLOWER SECTION
Type
Power displayed on plate kW
Voltage displayed on plate V
Current displayed on plate A
Fan type Forward Backward Forward Backward
Displayed coupling ref mm
Alignment checked Yes No Yes No
Fan speed rpm
Averaged measured amps A
Shaft mechanical mower
(Refer to airfl ow balancing)
W
Operating point checked Yes No Yes No
Read airfl ow m
3
/h
(6) EXTERNAL SENSOR CHECKS
Check electrical connections Yes No
Check and record temp. in
menu 2110
Yes No
100% Fresh Air 100% return Air
Supply temperature °C °C
Return temperature °C °C
Outdoor temperature °C °C
(7) MIXING AIR DAMPERS CHECKS
Dampers open & close freely % Minimum FA
Power
exhaust checked
Enthalpy sensor(s) checked
Yes No % Yes No Yes No
(5) AIRFLOW PRESSURE SENSOR CHECK
Measured pressure drop
Set points adjusted
Yes No
mBar
If yes enter new values
(3) CLIMATIC™ CONFIGURATION CHECK
CLIMATIC™ 60 Confi gured according to the options and specifi cations
Yes No