Page 138 - IOM / ROOFTOP BALTIC Series - 0704 - E
ELECTRICAL DATA - CONTROL variables
STANDARD
Logical Output Board
(2 outputs : 1 assigned, 1 customized)
DO 1 - Alarm, General
DO 2 - Customized
(choose 1 output between those 7 possibilities)
- Alarm, Filters
- Alarm, Blower
- Alarm, Compressors
- Alarm, Heaters
- Heating mode
- Alarm, Hot Water Coil Freezing
- Zone A, Activated
- Zone B, Activated
- Zone C, Activated
- Zone Uno., Activated
- Zone BMS, Activated
- Free, for BMS
Logical Input Board
(4 inputs : 2 assigned, 2 customized)
DI 1 - ON/OFF
DI 2 - Reset alarm
DI 3 & 4 - Customized
(choose, for each input (2) between those 12 possibilities)
- Disable, Compressors & Heaters
- Disable, Compressors
- Disable, Heaters
- Disable, Cooling
- Disable, Heating
- Fault contact, Humidifier
- 10 % Fresh air
- 20 % Fresh air
- 30 % Fresh air
Those contacts add up
- 40 % Fresh air
- 50 % Fresh air
- Free, for BMS
ADVANCED CONTROL PACK OR TCB
Logical Output Board
(4 outputs : 0 assigned, 4 customized)
DO 3 to 6 - Customized (choose, for each input (4) between those 7 possibilities)
- Alarm, Filters
- Alarm, Blower
- Alarm, Compressors
- Alarm, Heaters
- Heating mode
- Alarm, Hot Water Coil Freezing
- Zone A, Activated
- Zone B, Activated
- Zone C, Activated
- Zone Uno., Activated
- Zone BMS, Activated
- Free, for BMS
Logical Input Board
(4 outputs: 0 assigned, 4 customized)
DI 5 to 8 - Customized (choose, for each input (4) between those 12 possibilities)
- Disable, Compressors & Heaters
- Disable, Compressors
- Disable, Heaters
- Disable, Cooling
- Disable, Heating
- Fault contact, Humidifier
- 10 % Fresh air
- 20 % Fresh air
- 30 % Fresh air Those contacts add up
- 40 % Fresh air
- 50 % Fresh air
- Free, for BMS
Analogue Input Board
(4 outputs : 0 assigned, 2 customized)
AI 1 & 2 - Customized (choose, for each input (4) between those 4 possibilities)
- Override room temp set point -5 +5°C (4-20mA)
- Override fresh air set point 0-100% (4-20mA)
- Free temperature (NTC probe)
- Free relative humidity (4-20mA)
{
{

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox Baltic BHK 070 and is the answer not in the manual?

Lennox Baltic BHK 070 Specifications

General IconGeneral
BrandLennox
ModelBaltic BHK 070
CategoryAir Conditioner
LanguageEnglish

Related product manuals