! If temperature entering gas burner section is below -5°C, the life expectancy of the gas burner can be
significantly affected due to corrosive condensation.
Table 4.26
Gas Power Heating Power abs. Number
SIZE Input capacity Electrical of stages
kW kW kW
020 Standard heat
High heat
025 Standard heat
High heat
030 Standard heat
High heat
035 Standard heat
High heat
040 Standard heat
High heat
045 Standard heat
High heat
050 Standard heat
High heat
20 18,6 0,2 2
33 30,7 0,2 2
20 18,6 0,2 2
33 30,7 0,2 2
20 18,6 0,2 2
46 42,8 0,2 2
20 18,6 0,2 2
46 42,8 0,2 2
33 30,7 0,2 2
60 55,8 0,2 2
33 30,7 0,2 2
60 55,8 0,2 2
33 30,7 0,2 2
60 55,8 0,2 2
PERFORMANCES
ELECTRIC HEATER
BCK = Cooling only rooftop BHK = Heat pump rooftop
Available Number Temperature
SIZE capacity of rise at
kW Stages nominal air flow
020
025
030
Table 4.25
12 2 stages stage 1 # 5,2°C
stage 2 # 10,4°C
24 2 stages stage 1 # 10,4°C
stage 2 # 20,9°C
36 0 - 100% 50% # 15,7°C
100% # 31,3°C
12 2 stages stage 1 # 4,2°C
stage 2 # 8,4°C
24 2 stages stage 1 # 8,4°C
stage 2 # 16,7°C
36 0 - 100% 50% # 12,5°C
100% # 25,1°C
24 2 stages stage 1 # 7°C
stage 2 # 13,9°C
36 2 stages stage 1 #10,4°C
stage 2 # 20,9°C
48 0 - 100% 50% # 13,9°C
100% # 27,9°C
Available Number Temperature
SIZE capacity of rise at
kW Stages nominal air flow
035
040
045
050
Table 4.47
24 2 stages stage 1 # 6°C
stage 2 # 11,9°C
36 2 stages stage 1 # 9°C
stage 2 # 17,9°C
48 0 - 100% 50% # 11,9°C
100% # 23,9°C
27 2 stages stage 1 # 3,9°C
stage 2 # 11,8°C
45 2 stages stage 1 # 7,8°C
stage 2 # 19,6°C
54 0 - 100% 50% # 11,8°C
100% # 23,5°C
27 2 stages stage 1 # 3,4°C
stage 2 # 10,4°C
45 2 stages stage 1 # 7,0°C
stage 2 # 17,4°C
54 0 - 100% 50% # 10,4°C
100% # 20,9°C
27 2 stages stage 1 # 3,1°C
stage 2 # 9,4°C
45 2 stages stage 1 # 6,3°C
stage 2 # 15,7°C
54 0 - 100% 50% # 9,4°C
100% # 18,8°C
GAS BURNER
BGK = Cooling only rooftop with gas fired heater BDK = Heat pump rooftop with gas fired heater
ACCESSORIES HEATING CAPACITIES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox BALTIC Series and is the answer not in the manual?

Lennox BALTIC Series Specifications

General IconGeneral
BrandLennox
ModelBALTIC Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals