Page 44 - Application Guide 04-2003 / Rooftop BALTIC Series
BCK = Cooling only rooftop BHK = Heat pump rooftop BGK = Cooling only rooftop with gas fired heating BDK = Heat pump rooftop with gas fired heating
EU4 Hot Electric Multi-
Economiser Filters water coil (Pa) heater (Pa) roofcurb directional
SIZE Airflow (Pa) (Pa) S H S M H (Pa) (Pa)
2900 8 0 22 31 37 38 40 16 23
020 3600 13 6 32 46 55 57 59 24 35
4300 18 12 43 61 76 79 81 35 50
3600 13 6 32 46 55 57 59 24 35
025 4500 20 14 46 66 83 85 88 38 55
5400 28 25 63 89 117 120 123 55 79
4300 11 1 29 40 42 45 47 19 18
030 5400 17 8 43 59 63 66 69 29 28
6500 24 15 59 80 89 93 96 42 41
5000 14 5 37 51 55 58 61 25 24
035 6300 23 14 56 76 84 88 91 39 38
7600 33 24 77 105 119 123 127 58 56
5800 18 0 35 46 50 53 57 16 23
040 7200 28 6 51 67 74 78 82 25 35
8600 40 12 70 91 101 106 111 36 51
6500 23 3 43 56 61 65 69 20 29
045 8100 36 10 63 82 91 95 100 32 45
9700 51 18 87 113 126 131 137 46 64
7200 28 6 51 67 74 78 82 25 35
050 9000 44 14 76 99 110 115 120 39 55
10 800 63 25 105 136 154 160 166 56 80
Table 5.19
PERFORMANCES ACCESSORIES PRESSURE DROPS