EasyManuals Logo
Home>Lennox>Air Conditioner>CAMH025SM1M

Lennox CAMH025SM1M User Manual

Lennox CAMH025SM1M
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
• 8 •
CAMH060DM1M CAMH075DM1M CAMH085DM1M
59,6 71 85,3
56,2 67,7 80,8
23,8 28,3 35,4
22 27,3 32,6
2145 2145 2145
2813 2813 2813
895 895 895
910 955 975
CASH060DM1M CASH075DM1M CASH085DM1M
1 / Scroll BLDC +
2 / Scroll Tamdem
1 / Scroll BLDC +
2 / Scroll Tamdem
1 / Scroll BLDC +
2 / Scroll Tamdem
2 / EC Plug Fan 2 / EC Plug Fan 2 / EC Plug Fan
16800 20000 23400
30 30 30
1410 1410 1410
2813 2813 2813
895 895 895
575 595 615
5/8" + 5/8" 5/8" + 5/8" 5/8" + 5/8"
1 1/8" + 1 1/8" 1 1/8" + 1 3/8" 1 3/8" + 1 3/8"
CAIH060DM1M CAIH075DM1M CAIH085DM1M
2 / EC Plug Fan 2 / EC Plug Fan 2 / EC Plug Fan
6200 / 12500 6700 / 13500 7500 / 15000
100 / 700 100 / 700 100 / 750
836 836 836
2813 2813 2813
895 895 895
340 360 360
5/8" + 5/8" 5/8" + 5/8" 5/8" + 5/8"
1 1/8" + 1 1/8" 1 1/8" + 1 3/8" 1 3/8" + 1 3/8"
150 150 150
25 25 25
80 80 80
170 202 202
Installation Manual • COMPACTAIR ADV IOM-MIL157E-0418
SET
Cooling capacity (*) Kw
Heating capacity (**) Kw
Nominal absorbed power (Cold) (*) Kw
Nominal absorbed power (Heating) (**) Kw
DIMENSIONS
Height mm
Width mm
Depth mm
NET WEIGHT Kg
OUTDOOR UNIT
COMPRESSOR Nº / type
FAN
Nominal air ow m
3
/h
Available preassure Pa
DIMENSIONS
Height mm
Width mm
Depth mm
NET WEIGHT Kg
PIPING CONNECTIONS
Liquid inches
Gas inches
INDOOR UNIT
FAN Nº / type
Air ow (Min / Max) m
3
/h
Available preassure (***) Pa
DIMENSIONS
Height mm
Width mm
Depth mm
NET WEIGHT Kg
PIPING CONNECTIONS
Liquid inches
Gas inches
NET WEIGHT OF OPTIONALS
Free-cooling Kg
Electrical Heater Kg
Filter M5+F7 Kg
Return fan Kg
1.- GENERAL CHARACTERISTICS
1.3.- PHYSICAL DATA.
(*) At 120 rps, air intake temperature in indoor exchanger: 27ºC BS / 19ºC BH.
(*) At 120 rps, air intake temperature in outdoor exchanger: 35ºC BS.
(**) At 120 rps, air intake temperature in indoor exchanger: 20ºC BS / 12ºC BH.
(**) At 120 rps, air intake temperature in outdoor exchanger: 7ºC BS / 6ºC BH.
(***) Adjustable by DS terminal.
BS - Dry bulb temperature.
BH - Wet bulb temperature.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox CAMH025SM1M and is the answer not in the manual?

Lennox CAMH025SM1M Specifications

General IconGeneral
BrandLennox
ModelCAMH025SM1M
CategoryAir Conditioner
LanguageEnglish

Related product manuals