• 9 •
CAMH025SM1M CAMH035SM1M CAMH035SM1M
400V/ 3Ph 400V/ 3Ph 400V/ 3Ph
13,9 18,6 24,5
24,6 33,4 43,6
CASH025SM1M CASH035SM1M CASH035SM1M
400V/ 3Ph 400V/ 3Ph 400V/ 3Ph
8,5 13 18,8
2,7 2,86 2,86
11,2 15,86 21,66
16,2 24,9 35,03
4,2 4,3 4,3
20,4 29,2 39,3
CAIH025SM1M CAIH035SM1M CAIH035SM1M
400V/ 3Ph 400V/ 3Ph 400V/ 3Ph
2,7 2,7 2,9
4,2 4,2 4,3
CAMH025SM1M CAMH035SM1M CAMH035SM1M
10 10 10
15 15 15
20 20 20
14,3 14,3 14,3
21,5 21,5 21,5
28,6 28,6 28,6
Installation Manual • COMPACTAIR ADV IOM-MIL157E-0418
1.4.- ELECTRICAL DATA.
ELECTRICAL CONSUMPTIONS.
SET
Voltage V/f (50 Hz)
Total maximum power kW
Total maximum current A
OUTDOOR UNIT
Voltage V/f (50 Hz)
MAXIMUM POWER CONSUMED
Maximum compressor power kW
Outdoor fan power kW
Total maximum power kW
MAXIMUM CURRENT
Maximum compressor current A
Outdoor fan current A
Total maximum current A
INDOOR UNIT
Voltage V/f (50 Hz)
Total maximum power kW
Total maximum current A
OPTIONAL ELECTRICAL COIL
POWER
Standard kW
Medium kW
High kW
CURRENT
Standard A
Medium A
High A
1.- GENERAL CHARACTERISTICS