EasyManuals Logo
Home>Lennox>Air Handlers>CBA25UHV

Lennox CBA25UHV User Manual

Lennox CBA25UHV
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
Page 21
#4 Pins Jumpered
A- Motor ramps up to 82%.
B- Motor then runs at 82% for approximately 7-1/2 min-
utes. If demand has not been satised after 7-1/2 min-
utes,
C- Motor runs at 100% until demand is satised.
D- Once demand is met, motor ramps down to stop.
A
B
OFF
OFF
C
D
COOLING DEMAND
7 1/2 MIN
82% CFM
100%
CFM
Check-out Procedures
NOTE – Refer to outdoor unit installation instructions for sys-
tem start-up instructions and refrigerant charging instructions.
PRE-START-UP CHECKS
Is the air handler properly and securely installed?
If horizontally congured, is the unit sloped up to 5/8
inch toward drain lines?
Will the unit be accessible for servicing?
Has an auxiliary pan been provided under the unit with
separate drain for units installed above a nished ceil-
ing or in any installation where condensate overow
could cause damage?
Have ALL unused drain pan ports been properly
plugged?
Has the condensate line been properly sized, run,
trapped, pitched, and tested?
Is the duct system correctly sized, run, sealed, and in-
sulated?
Have all cabinet openings and wiring been sealed?
Is the indoor coil factory-installed TXV properly sized for
the outdoor unit being used?
Have all unused parts and packaging been disposed
of?
Is the lter clean, in place, and of adequate size?
Is the wiring neat, correct, and in accordance with the
wiring diagram?
Is the unit properly grounded and protected (fused)?
Is the thermostat correctly wired and in a good location?
Are all access panels in place and secure?
CHECK BLOWER OPERATION
Set thermostat to FAN ON.
The indoor blower should come on.
CHECK COOLING OPERATION
Set thermostat to force a call for cooling (approximately
5ºF lower than the indoor ambient temperature).
The outdoor unit should come on immediately and the
indoor blower should start between 30 - 60 seconds later.
Check the air ow from a register to conrm that the
system is moving cooled air.
Set the thermostat 5ºF higher than the indoor tempera-
ture. The indoor blower and outdoor unit should cycle
o󰀨.
CHECK ELECTRIC HEAT (IF USED)
Set thermostat to call for auxiliary heat (approximate-
ly 5°F above ambient temperature). The indoor blow-
er and auxiliary heat should come on together. Allow a
minimum of 3 minutes for all sequencers to cycle on.
Set the thermostat so that it does not call for heat. Allow
up to 5 minutes for all sequencers to cycle o󰀨.
Maintenance
IMPORTANT
Do not operate system without a lter. A lter is required
to protect the coil, blower, and internal parts from
excessive dirt and dust. The lter is placed in the return
duct by the installer.
Inspect air lters at least once a month and replace or
clean as required. Dirty lters are the most common
cause of inadequate heating or cooling performance.
Replace disposable lters. Cleanable lters can be
cleaned by soaking in mild detergent and rinsing with
cold water.
Install new/clean lters with the arrows on the side point-
ing in the direction of air ow. Do not replace a clean-
able (high velocity) lter with a disposable (low velocity)
lter unless return air system is properly sized for it.
If water should start coming from the secondary drain
line, a problem exists which should be investigated and
corrected. Contact a qualied service technician.
Repairing or Replacing Cabinet Insulation
IMPORTANT
DAMAGED INSULATION MUST BE REPAIRED OR
REPLACED before the unit is put back into operation.
Insulation loses its insulating value when wet, damaged,
separated or torn.
Matte- or foil-faced insulation is installed in indoor equip-
ment to provide a barrier between outside air conditions
(surrounding ambient temperature and humidity) and the
varying conditions inside the unit. If the insulation barrier
is damaged (wet, ripped, torn or separated from the cabi-
net walls), the surrounding ambient air will a󰀨ect the inside
surface temperature of the cabinet.
The temperature/humidity di󰀨erence between the inside
and outside of the cabinet can cause condensation on the
inside or outside of the cabinet which leads to sheet metal
corrosion and, subsequently, component failure.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox CBA25UHV and is the answer not in the manual?

Lennox CBA25UHV Specifications

General IconGeneral
BrandLennox
ModelCBA25UHV
CategoryAir Handlers
LanguageEnglish

Related product manuals