NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure 9 - Minimum Mantel Clearances
All Models
Combustible Shelf Height - Inches (millimeters)
Secure Vent Secure Flex (flex elbow)
Top Vent *53-1/2 (1359) *55-1/4 (1403)
Rear Vent *40-1/4 (1022) *40-1/4 (1022)
Figure 10 - Minimum Distance to Side Wall
MINIMUM CLEARANCES TO COMBUSTIBLES
Appliance And Vent Clearances
The appliance is approved with zero clearance to combustible materials on
all sides (as detailed in Table 5), with the following exception: When the
unit is installed with one side flush with a wall, the wall on the other
side of the unit must not extend beyond the front edge of the unit. In
addition, when the unit is recessed, the side walls surrounding the unit
must not extend beyond the front edge of the unit (see Figure 3).
MINIMUM CLEARANCES* Inches (millimeters)
Back 1/2 in. (13)
0 (0) from Spacers Or Dimples
Sides 1/2 in. (13)
0 (0) from Spacers Or Dimples **
Top Spacers 0 (0)
Floor 0 (0)
From Bottom of Unit To Ceiling 64 (1626)
Vent 3 (76)
Top* / 1 (25.4) Sides & Bottom
SERVICE CLEARANCES Feet (meters)
Front 3 feet (0.9 meters)
Table 5
*Note: 3 in. (75 mm) above any horizontal/inclined vent component.
**Note: See Page 9, Step 1 for clearance requirements to the nailing ange
located at each side of the unit and any screw heads adjacent to it.
Hearth Extension - A hearth extension is not required with this appliance.
If a hearth extension is used, do not block the lower control compartment
door. Any hearth extension used is for appearance only and does not have
to conform to standard hearth extension installation requirements.
Shelf Height - To provide for the lowest possible shelf surface, use the
alternate rear vent outlet, the venting attached to the top vent should be
routed in a way to minimize obstructions to the space above the appliance.
Do not insulate the space between the appliance and the area above
it (see Figure 8). The minimum height from the base of the appliance to
the underside of combustible materials used to construct a utility shelf in
this fashion is shown in Figure 8.
The appliance should be mounted on a fully supported base extending
the full width and depth of the unit. The appliance may be located on
or near conventional construction materials. However, if installed on
combustible materials, such as carpeting, vinyl tile, etc., a metal or wood
barrier covering the entire bottom surface must be used.
Wall Finishes / Surrounds / Mantels
Note: Combustible wall finish materials and/or surround materials must not
be allowed to encroach the area defined by the appliance front face (black
sheet metal). Never allow combustible materials to be positioned in front of
or overlapping the appliance face (see Figures 63 and 64 on Page 33).
Non-combustible materials, such as surrounds and other appliance trim,
may be installed on the appliance face with these exceptions: they must not
cover any portion of the removable glass panel or control compartment.
Vertical installation clearances to combustible mantels vary according to the
depth of the mantel. See Figure 9. Mantels constructed of non-combustible
materials may be installed at any height above the appliance opening;
however, do not allow anything to hang below the fireplace hood.
* Includes 3” clearance to combustibles (required above vent components)
Combustible materials may project beyond one side of the fireplace opening
as long as they are kept within the shaded areas illustrated here.
Figure 8 -
Shelf Height Minimum Clearances With Top Venting
12 (305) MANTEL
10 (254) MANTEL
8 (203) MANTEL
6 (152) MANTEL
4 (102) MANTEL
4
(102)
14
(356)
12
(305)
10
(254)
2 (51) MANTEL
TOP OF
APPLIANCE
6
(152)
NOTE - Hood shown as positioned in louvered
front model. The hood position in the flush
faced front model is lower than shown.
8
(203)
MANTEL CLEARANCES
Inches (mm)
17"
14"
Min. Distance To
Unprotected
Perpendicular Side Wall
8-1/4"
45
°
Combustible Materials
Allowed In Shaded
Area “Safe Zone”
12"
5"
Top View Of
Fireplace
Side
Wall
Side
Wall
Min. Distance
To Protected
Perpendicular
Side Wall
Shelf Above Fireplace With Rear Venting
Do not insulate the
space between the
appliance and the
area above it.
Shelf Height
(
see table)
Shelf Height
(
see table)
Do not insulate the
space between the
appliance and the
area above it.
Shelf Above Fireplace With Top Venting