Page 50
VI-MAINTENANCE
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could
result in dangerous operation, serious injury, death
or property damage.
Improper servicing could result in dangerous
operation, serious injury, death, or property damage.
Before servicing, disconnect all electrical power to
furnace.
When servicing controls, label all wires prior
to disconnecting. Take care to reconnect wires
correctly. Verify proper operation after servicing.
At the beginning of each heating season, system should
be checked as follows by a qualied service technician:
Blower
Check the blower wheel for debris and clean if necessary.
The blower motors are prelubricated for extended bearing
life. No further lubrication is needed.
WARNING
The blower access panel must be securely in place
when the blower and burners are operating. Gas
fumes, which could contain carbon monoxide, can
be drawn into living space resulting in personal
injury or death.
Filters
All air lters are installed external to the unit. Filters should
be inspected monthly. Clean or replace the lters when
necessary to ensure proper furnace operation. Table 27
lists recommended lter sizes.
IMPORTANT
If a higheciency lter is being installed as part of
this system to ensure better indoor air quality, the
lter must be properly sized. Higheciency lters
have a higher static pressure drop than
standardeciency glass/foam lters. If the pressure
drop is too great, system capacity and performance
may be reduced. The pressure drop may also cause
the limit to trip more frequently during the winter and
the indoor coil to freeze in the summer, resulting in
an increase in the number of service calls.
Before using any lter with this system, check the
specications provided by the lter manufacturer
against the data given in the appropriate Lennox
Product Specications bulletin. Additional
information is provided in Service and Application
Note ACC002 (August 2000).
TABLE 26
Cabinet Width Filter Size
17-1/2”
16 x 25 x 1(1)
21”
Exhaust and air intake pipes
Check the exhaust and air intake pipes and all connec-
tions for tightness and to make sure there is no blockage.
NOTE - After any heavy snow, ice or frozen fog event the
furnace vent pipes may become restricted. Always check
the vent system and remove any snow or ice that may be
obstructing the plastic intake or exhaust pipes.
Electrical
CAUTION
Failure to use properly sized wiring and circuit
breaker may result in property damage. Size wiring
and circuit breaker(s) per Product Specications
bulletin (EHB) and unit rating plate.
1 - Check all wiring for loose connections.
2 - Check for the correct voltage at the furnace (furnace
operating).
3 - Check amp-draw on the blower motor.
Motor Nameplate__________Actual__________
Winterizing and Condensate Trap Care
1 - 1 - Turn o power to the furnace.
2 - Have a shallow pan ready to empty condensate
water.
3 - Remove the clean out cap from the condensate trap
and empty water. Inspect the trap then reinstall the
clean out cap.
Condensate Hose Screens (Figure 57)
Check the condensate hose screens for blockage and
clean if necessary.
1 - Turn o power to the unit.
2 - Remove hoses from cold end header box. Twist
and pull screens to remove.
3 - Inspect screens and rinse with tap water if needed.
4 - Reinstall screens, reconnect hoses and turn on
power to unit.
Hose
FIGURE 57