EasyManuals Logo
Home>Lennox>Furnace>G40DF Series

Lennox G40DF Series User Manual

Lennox G40DF Series
35 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
Page 9
2 − After opening is cut, set additive base into opening.
3 − Check fiberglass strips on additive base to make sure
they are properly glued and positioned.
4 Lower supply air plenum into additive base until ple-
num flanges seal against fiberglass strips.
NOTE − Be careful not to damage fiberglass strips.
Check for a tight seal.
5 − Set the furnace over the plenum.
6 − Ensure that the seal between the furnace and plenum
is adequate.
G40DF(X)UNIT
SUPPLY AIR PLENUM
ADDITIVE BASE
PROPERLY
SIZED FLOOR
OPENING
FIGURE 6
Installation on Cooling Cabinet
1 Refer to reverse−flow coil installation instructions for
correctly sized opening in floor and installation of cabi-
net.
2 When cooling cabinet is in place, set and secure the
furnace according to the instructions that are provided
with the cooling coil. Secure the furnace to the cabinet.
3 − Seal the cabinet and check for air leaks.
Return Air Opening −− Downflow Units
The following steps should be taken when installing ple-
num:
1 Bottom edge of plenum should be flanged with a
hemmed edge (See figure 7).
2 − Fiberglass sealing strips should be used.
SECURE FROM
OUTSIDE CABINET
HEMMED EDGE
PLENUM
FIBERGLASS SEALING
STRIP
(Field Provided)
CABINET SIDE PANEL
Side View
FIGURE 7
3 − In all cases, plenum should be secured to top flanges
of furnace with sheet metal screws.
4 In closet installations, it may be impossible to install
sheet metal screws from the outside. In this case,
make plenum with a removable front and install
screws from the inside (See figure 8).
5 − Make certain that an adequate seal is made.
SECURE FROM
INSIDE CABINET
HEMMED EDGE
FIBERGLASS
SEALING STRIP
(Field Provided)
CABINET SIDE
PANEL
PLENUM
Side View
FIGURE 8
Setting Equipment
WARNING
Do not install the furnace on its front or its back. Do
not connect the return air ducts to the back of the fur-
nace. Doing so will adversely affect the operation of
the safety control devices, which could result in per-
sonal injury or death.
Install the G40DF(X) gas furnace as shipped. Do not
install the furnace horizontally.
Select a location that allows for the required clearances
that are listed on the unit nameplate. Also consider gas
supply connections, electrical supply, vent connection,
and installation and service clearances [24 inches (610
mm) at unit front]. The unit must be level.
NOTE − 1/3 hp blower motors are equipped with four flex-
ible mounting legs, and 1/2 hp blower motors are equipped
with three flexible legs and one rigid leg. The rigid leg is
equipped with a shipping bolt and a flat white plastic wash-
er (rather than the rubber mounting grommet used with a
flexible mounting leg). The bolt and washer must be re-
moved before the furnace is placed into operation. Af-
ter the bolt and washer have been removed, the rigid leg
will not touch the blower housing.
NOTE − G40DF−36C−110 units include a bracket which sta-
bilizes the blower motor during shipping. The bracket is se-
cured to the blower housing by two screws. This bracket
must be removed prior to placing the unit into opera-
tion. See figure 1.
Downflow Application
Allow for clearances to combustible materials as indi-
cated on the unit nameplate. Minimum clearances for
closet or alcove installations are shown in figure 9.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox G40DF Series and is the answer not in the manual?

Lennox G40DF Series Specifications

General IconGeneral
BrandLennox
ModelG40DF Series
CategoryFurnace
LanguageEnglish

Related product manuals