Troubleshooting
To verify motor operation see steps below:
1− Remove J48 (5 pin power plug) from P48 on the mo-
tor.
2− With the power on at the furnace and door switch de-
pressed, use a test meter to verify 120V between pins
4 and 5 on J48.
3− Reconnect J48 to P48 on the motor.
4− Remove J49 (4 pin low voltage connector) from P49
on the motor.
5− Using test jumpers, apply 24V to pins 3 and 4 on P49
on the motor.
Note: Do not apply 24V to pins 2 and 4 on P49. Doing so
will cause permanent damage to the motor.
6− Motor should run at 75%.
7− Test is complete. Remove jumpers and reconnect
plugs.
Another option is to use the TECMate PRO with the 16 to
4 pin adaptor. The use of the TECMate PRO isolates the
motor from the integrated control. Follow the instructions
provided with the kit. If the motor runs do not replace.
FIGURE 10
BLOWER B3 HARNESS CONNECTORS
MOTOR with IINTEGRATED
CONTROLLER
SHAFT
P49 4 Pin
P48 5 Pin
P48 5 Pin
P49 4 Pin
J48 Connector
installed on motor
P49 4 Pin
120v
0
240v
5
4
3
2
1
J48 Connector
24v Transformer
J49 Connector

Table of Contents

Other manuals for Lennox G71MPP SERIES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox G71MPP SERIES and is the answer not in the manual?

Lennox G71MPP SERIES Specifications

General IconGeneral
BrandLennox
ModelG71MPP SERIES
CategoryFurnace
LanguageEnglish

Related product manuals