Page 60
CALL FOR COOLING
1st Stage Cooling
Request Received
Energize 1st Stage
Cooling Contactor
(Compressor & Fan)
2nd Stage
Cooling
Request?
YES
2nd Stage
Cooling Request
Still Active?
DeEnergize 1st
Stage Cooling
Contactor
(Compressor & Fan)
YES
1st Stage
Cooling Request
Still Active?
NO
YES
YES
Energize 2nd Stage
Cooling Contactor
(Compressor & Fan)
1st Stage
Cooling Request
Still Active?
DeEnergize 2nd
Stage Cooling
Contactor
(Compressor & Fan)
Energize and
Low Cooling mode
(High Cooling mode)
(High Cooling mode)
Per Ramping Profile
NO
NO
YES
NO
5
1
2
1
2
2
2
1
Indoor Blower On
After 2second delay
Energize Indoor Blower
(Per Ramping Profile)
Energize Indoor Blower
Maintain Indoor Blower
Maintain Indoor Blower at
DeEnergize Indoor Blower
2nd stage cooling operation requires a 2stage thermostat, a 2stage cooling system and jumpers
W915 must be be cut. The control will not respond to a 2nd stage cooling request unless a 1st stage
cooling request is active
Indoor blower cooling mode and high cooling mode have a specific ON, OFF and speed ramping
profiles. The specific profile is selected using the DIP switches on the control.

Table of Contents

Other manuals for Lennox G71MPP SERIES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox G71MPP SERIES and is the answer not in the manual?

Lennox G71MPP SERIES Specifications

General IconGeneral
BrandLennox
ModelG71MPP SERIES
CategoryFurnace
LanguageEnglish

Related product manuals