SPECIFICATIONS
Model No. HP29-018 HP29-024 HP29-030 HP29-036−1ph HP29-036−3ph
Net face area
Outer coil 11.41 (1.06) 11.41 (1.06) 15.21 (1.43) 15.21 (1.41) 15.21 (1.41)
Outdoor
Net
face
area
sq. ft. (m
2
)
Inner coil - - - - - - - - 5.44 (.51) 14.50 (1.35) 5.44 (.51)
Outdoor
Coil
Tube diam.−in. (mm) no. of rows
5/16 (7.9)  1 5/16 (7.9)  1 5/16 (7.9)  1 5/16 (7.9)  2 5/16 (7.9)−1.37
Coil
Fins per inch (m) 22 (866) 22 (866) 18 (709) 18 (709) 22 (866)
Diameter−in. (mm) no. of blades 18 (457)  3 18 (457)  3 18 (457)  4 18 (457)  4 18 (457) − 4
Outdoor
Motor hp (W) 1/6 (124) 1/6 (124) 1/6 (124) 1/6 (124) 1/6 (124)
Outdoor
Coil
F
Cfm (L/s) 2400 (1135) 2400 (1135) 2550 (1203) 2530 (1193) 2500 (1180)
Coil
Fan
Rpm 1105 1105 1115 1110 1100
Watts 180 180 190 195 200
*Refrigerant charge furnished (HCFC-22) 4 lbs. 2 oz. (1.86 kg) 4 lbs. 1oz. (1.83 kg) 5 lbs.12 oz. (2.6 kg) 7 lbs.2 oz. (3.22kg) 6 lbs 0 0z. (2.72kg)
Liquid line  in. (mm) o.d. conn. (sweat) **3/8 to 5/16 (8) **3/8 to 5/16 (8) **3/8 to 5/16 (8) 3/8 (9.5) 3/8 (9.5)
Vapor line  in. (mm) o.d. conn. (sweat) 5/8 (15.9) 5/8 (15.9) 3/4 (19.1) 3/4 (19.1) 3/4 (19.1)
Shipping weight  lbs. (kg) 1 package 152 (69) 152 (69) 161 (73) 173 (78.5) 193 (88)
*Refrigerant charge sufficient for 15 ft. (4.5 m) length of refrigerant lines.
**5/16 to 3/8 reducer coupling supplied with unit.
SPECIFICATIONS
Model No. HP29-042−1ph HP29-042−3ph HP29-048 HP29-060
Outer coil 15.21 (1.41) 15.21 (1.41) 15.21 (1.41) 21.11 (1.96)
Outdoor
Net face area - sq. ft. (m
2
)
Inner coil 14.50 (1.35) 5.44 (.51) 14.50 (1.35) 20.31 (1.9)
Outdoor
Coil
Tube diameter in. (mm) & no. of rows 5/16 (7.9) − 2 5/16 (7.9) − 1.37 5/16 (7.9)  2 5/16 (7.9)  2
Fins per inch (m) 18 (709) 22 (866) 18 (709) 18 (709)
Diameter  in. (mm) & no. of blades 18 (457) − 4 18 (457) − 4 18 (457)  4 18 (457)  4
Outdoor
Motor hp (W) 1/3 (249) 1/6 (124) 1/3 (249) 1/3 (249)
Outdoor
Coil
F
Cfm (L/s) 2975 (1403) 2500 (1180) 3020 (1425) 4330 (2043)
Coil
Fan
Rpm 1130 1100 1125 1075
Watts 310 200 330 420
*Refrigerant charge furnished (HCFC-22) 8 lbs. 5 0z. (3.76 kg) 7 lbs. 10 0z. (3.45 kg) 7 lbs. 12 oz. (3.51 kg) 11 lbs. 13 oz. (5.34kg)
Liquid line  in. (mm) o.d. connection (sweat) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
Vapor line  in. (mm) o.d. connection (sweat) 7/8 (22.2) 7/8 22.2) 7/8 (22.2) 1-1/8 (28.6)
Shipping weight  lbs. (kg) 1 package 182 (83) 199 (90.3) 190 (86.2) 254 (115.2)
*Refrigerant charge sufficient for 15 ft. (4.5 m) length of refrigerant lines.
ELECTRICAL DATA
Model No.
HP29−211−
1
HP29−211−
2
HP29−261−
1
HP29-261−
2
HP29-311 HP29-411 HP29-413
Line voltage data  60 hz
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/23v
3ph
460v
3ph
Rated load amps
8.6 7.9 9.8 10.1
13.7 16.2 10.3 4.3
Compressor Power factor .97 .97 .96 .96 .92 .90 .83 .83
Locked rotor amps 49.0 49.0 56.0 60.0 75.0 96.0 75.0 40.0
Outdoor Coil
Full load amps 1.1 1.1 1.1 1.1 1.1 1.1 1.1 0.55
Outdoor
Coil
Fan Motor
Locked rotor amps 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.0
Rec. maximum fuse or circuit breaker size (amps) 20 15 20 20 30 35 20 10
*Minimum circuit ampacity 11.9 11.0 13.5 13.8 18.4 21.4 14.0 6.5
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE  Extremes of operating range are plus 10% and minus 5% of line voltage.
ELECTRICAL DATA
Model No. HP29-461 HP29-463 HP29-511 HP29-513 HP29-651 HP29-653
Line voltage data  60 hz
208/230v
1ph
208/230v
3ph
460v
3ph
208/230v
1ph
208/230v
3ph
460v
3ph
575v
3ph
208/230v
1ph
208/230v
3ph
460v
3ph
575v
3ph
Rated load amps 17.5 12.8 6.4 23.4 14.0 7.1 5.8 26.9 17.3 9.0 7.1
Compressor Power factor .98 .93 .93 .98 .88 .88 .88 .98 .86 .86 .86
Locked rotor amps 92.0 87.0 44.0 110.0 91.0 46.0 37.0 123.0 128.0 64.0 51.0
Outdoor Coil
Full load amps 1.1 1.1 0.55 1.9 1.9 0.90 0.90 1.9 1.9 0.90 0.90
Outdoor
Coil
Fan Motor
Locked rotor amps 1.9 1.9 1.0 4.1 4.1 2.1 2.1 4.1 4.1 2.1 2.1
Rec. max. fuse or circuit breaker size (amps) 40 25 15 50 30 15 10 60 40 20 15
*Minimum circuit ampacity 23.0 17.1 8.6 31.2 19.4 9.8 8.2 35.5 23.5 12.2 9.8
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE  Extremes of operating range are plus 10% and minus 5% of line voltage.