Page 2
SPECIFICATIONS (Late Model)
Model No. HS26018 HS26024 HS26030 HS26036 HS26042 HS26048 HS26060
Net face area
Outer coil 11.9 (1.11) 11.9 (1.11) 16.0 (1.59) 16.0 (1.59) 16.0 (1.59) 18.2 (1.69) 21.6 (2.01)
sq. ft. (m
2
)
Inner coil 5.5 (0.51) 5.5 (0.51) 5.6 (0.52) 13.3 (1.24) 13.3 (1.24) 13.3 (1.24) 20.8 (1.93)
Condenser
Coil
Tube diameter in. (mm) 5/16 (7.9) 5/16 (7.9) 5/16 (7.9) 5/16 (7.9) 5/16 (7.9) 5/16 (7.9) 5/16 (7.9)
No. of rows 1.48 1.48 1.36 1.86 1.86 1.75 2
Fins per inch (m) 22 (866) 22 (866) 22 (866) 22 (866) 22 (866) 22 (866) 22 (866)
Dia. − in. (mm) no. of blades 20 (508) − 4 20 (508) − 4 24 (610) − 3 24 (610) − 3 24 (610) − 3
24 (610)
4
24 (610)
4
Motor hp (W) 1/10 (75) 1/6 (124) 1/6 (124) 1/6 (124) 1/6 (124) 1/4 (187) 1/4 (187)
on
enser
Fan Cfm (L/s) 2500 (1180) 2450 (1155) 3150 (1485) 3150 (1485) 3000 (1415) 3900 (1840) 4200 (1980)
Rpm 825 825 825 825 825 820 820
Watts 160 210 225 225 230 310 350
*Refrigerant HCFC22 charge furnished
4 lbs. 1 oz.
(1.84 kg)
4 lbs. 1 oz.
(1.84 kg)
5 lbs. 1 oz.
(2.30 kg)
5 lbs. 13 oz.
(2.64 kg)
6 lbs. 11 oz.
(3.03 kg)
7 lbs. 5 oz.
(3.32 kg)
10 lbs. 8 oz.
(4.76 kg)
Liquid line (o.d.) in. (mm) sweat 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
Suction line (o.d.) in. (mm) sweat 5/8 (16) 3/4 (19) 3/4 (19) 3/4 (19) 7/8 (22.2) 7/8 (22.2) 11/8 (28.6)
Shipping weight lbs. (kg) 1 package 177 (80) 185 (84) 192 (87) 221 (100) 231 (105) 274 (124) 308 (140)
*Refrigerant charge sufficient for 25 ft. (7.6 m) length of refrigerant lines.
ELECTRICAL DATA (Late Model)
Model No. HS26018 HS26024 HS26030 HS26036 HS26042
Line voltage data 60hz
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/230v
3ph
208/230v
1ph
208/230v
3ph
Rated load amps 8.4 10.3 13.5 16.0 10.3 18.0 12.5
Compressor Power factor 0.97 0.96 0.96 0.96 0.82 0.94 0.82
Locked rotor amps 47 56 72.5 88 77 104 88
Condenser Coil
Full load amps 0.8 1.1 1.1 1.1 1.1 1.1 1.1
Fan Motor
Locked rotor amps 1.6 2.0 2.0 2.0 2.0 2.0 2.0
Rec. max. fuse or circuit breaker size (amps) 15 20 30 35 20 40 25
*Minimum circuit ampacity 13 14 18 21.3 14 23.6 16.4
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE Extremes of operating range are plus 10% and minus 5% of line voltage.
ELECTRICAL DATA (Late Model)
Model No. HS26048 HS26060
Line voltage data 60hz
208/230v
1ph
208/230v
3ph
460v
3ph
208/230v
1ph
208/230v
3ph
460v
3ph
Rated load amps 23.7 13.5 7.4 28.8 17.4 9.0
Compressor Power factor .97 .87 .87 .97 .85 .85
Locked rotor amps 129 99 49.5 169 123 62
Condenser Coil
Full load amps 1.7 1.7 1.1 1.7 1.7 1.1
Fan Motor
Locked rotor amps 3.1 3.1 2.2 3.1 3.1 2.2
Rec. max. fuse or circuit breaker size (amps) 50 30 15 60 40 20
*Minimum circuit ampacity 31.4 18.6 10.4 37.7 23.5 12.4
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE Extremes of operating range are plus 10% and minus 5% of line voltage.