EasyManuals Logo
Home>Lennox>Accessories>LGH074

Lennox LGH074 Installation Instructions

Lennox LGH074
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
Page 57
LGH/LCH036, 048, 060, 072, 074
TABLE 33
APPROACH TEMPERATURE
LGH/LCH Unit
Liquid Temp. Minus
Ambient Temp.
036S & H Std.; 036S & H Reheat;
048S & H Std.;
072H Std.; 074H Std.
6°F + 1 (3.3°C + 0.5)
048S & H Reheat;
072H Reheat; 074H Reheat
7°F + 1 (3.9°C + 0.5)
060S & H Std.; 060S/H Reheat F + 1 (4.4°C + 0.5)
TABLE 34
SUBCOOLING TEMPERATURE
LGH/LCH Unit
Liquid Saturated Temp. Minus
Liquid Temperature
036U; 060U 15°F + 1 (8.C + 0.5)
048U 15.5°F + 1 (8.C + 0.5)
074U 16°F + 1 (8.C + 0.5)
F-Compressor Controls
See unit wiring diagram to determine which controls are
used on each unit. Optional controls are identified on
wiring diagrams by arrows at junction points.
1- High Pressure Switch (S4)
The compressor circuit is protected by a high
pressure switch which opens at 640 psig +
10 psig
(4413 kPa +
70 kPa) and automatically resets at 475
psig +
20 psig (3275kPa + 138 kPa).
2- Low Pressure Switch (S87)
The compressor circuit is protected by a loss of
charge switch. Switch opens at 40 psig +
5 psig (276
+ 34 kPa) and automatically resets at 90 psig + 5
psig (621 kPa +
34 kPa).
3- Freezestat (S49)
The compressor is protected by a freezestat located
on the indoor coil. The freezestat opens at 29F+3
(-2C+
2) and closes at 58F+4 (14C+2).
4- Compressor Crankcase Heater (HR1)
Crankcase heater must be energized at all times to
prevent compressor damage due to refrigerant
migration. Energize crankcase heater 24 hours before
unit start-up by setting thermostat so that there is no
cooling demand (to prevent compressor from cycling)
and apply power to unit.
5- Low Ambient Pressure Switch (S11)
Switch maintains adequate discharge pressure by
de-energizing condenser fan when liquid pressure
falls below 240 psig +
10 (1655 kPa+69). S11 is
installed in the liquid line. Switch closes to energize
condenser fan when pressure rises to 450 psig +
10
(3103kPa + 69).
6- Discharge Line Thermostat (S40)
3 through 5 Ton Non-Ultra Units Only
Switch opens when discharge line temperature
reaches 94F+
5 (34C+3) and closes when
temperature falls below 74F+
5 (23C+3). Prevents
crankcase heater operation in warm weather.
7- High Ambient Pressure Switch (S16)
Switch improves high ambient operation by
activating the TXV assist circuit. Switch closes at
550psig +
10 (3792kPa + 70kPa) and automatically
resets at 400 PSIG (2758kPa +
70kPa).
Cooling Operation
036S/H, 048S/H, 060S/H, 074H UNITS
This is a summary of cooling operation. Refer to the
sequence of operation provided in the Engineering
Handbook or Service Manual for more detail.
Note - During a dehumidification demand the blower
operates at low speed. Free cooling is locked-out during
reheat operation. Refer to hot gas reheat start-up and
operation section for details.
A-Two-Stage Thermostat
1-Economizer With Outdoor Air Suitable
Y1 Demand -
Compressor Off
Blower Low
Dampers modulate
Y2 Demand -
Compressor Off
Blower High
Dampers Modulate
Note - If dampers are at maximum open for three
minutes, compressor is energized at high speed and
blower stays on cooling high.
2-No Economizer or Outdoor Air Not Suitable
Y1 Demand -
Compressor Low
Blower Low
Dampers Minimum Position
Y2 Demand -
Compressor High
Blower High
Dampers Minimum Position

Other manuals for Lennox LGH074

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox LGH074 and is the answer not in the manual?

Lennox LGH074 Specifications

General IconGeneral
BrandLennox
ModelLGH074
CategoryAccessories
LanguageEnglish

Related product manuals