Shipping and Packing List
Package 1 of 1 contains:
1- Assembled unit
IMPORTANT - Hot gas reheat units require a specific
field-provided and installed humidity sensor.
Check unit for shipping damage. Receiving party should
contact last carrier immediately if shipping damage is found.
General
These instructions are intended as a general guide
and do not supersede local codes in any way.
Authorities having jurisdiction should be consulted
before installation.
The LGH092, 094, 102, 120, 122, 150 & 152
gas/electric packaged rooftop unit is available in
130,000, 180,000, or 240,000 Btuh heating inputs.
The LCH092, 094, 102, 120, 122, 150 & 152 cooling
packaged rooftop unit is the same basic design as the
LGH unit except for the heating section. Optional
electric heat is factory- or field-installed in LCH units.
Ultra high efficiency units have a tandem refrigerant
circuit. High and standard efficiency units have two
typical circuits.
High and standard efficiency units are equipped with a
lightweight, all-aluminum condenser coil; an optional,
traditional fin/tube condenser coil is available. Ultra
high efficiency units are equipped with a traditional
fin/tube condenser coil.
High and standard efficiency units are available with an
optional hot gas reheat coil which provides a
dehumidifying mode of operation. Refer to Reheat
Operation section.
Ultra high efficiency units are available with an optional
direct drive blower or belt drive blower equipped with an
optional supply air inverter. Standard and high efficiency
units are available with a belt drive blower equipped with
an optional supply air inverter. The blower will operate at
lower speeds when demand is low and increase to higher
speeds when demand is high. Refer to Inverter and Direct
Drive Start−Up section.
The following examples show the model numbers of ten
ton units with blower options.
LGH/LCH120H4B Belt drive
LGH/LCH120H4M Belt drive with inverter
LGH/LCH122U4M Belt drive with inverter
LGH/LCH122U4E Direct drive
All units are available using R410A, an ozone-friendly HFC
refrigerant. Refer to the Cooling Start-Up section for
precautions when installing unit.
Safety
See table 1 for unit clearances.
WARNING
Electric shock hazard and danger of
explosion. Can cause injury, death or
product or property damage. Turn off
gas and electrical power to unit before
performing any maintenance or
servicing operations on the unit. Follow
lighting instructions attached to unit
when putting unit back into operation
and after service or maintenance.
UNIT CLEARANCES
C
D
B
A
FIGURE 1
Optional
Outdoor
Air Hood
TABLE 1
UNIT CLEARANCES
1
Unit
Clearance
A
in.(mm)
B
in.(mm)
C
in.(mm)
D
in.(mm)
Top
Clearance
Service
Clearance
60
(1524)
36
(914)
36
(914)
60
(1524)
Unob
structed
Clearance to
Combus
tibles
36
(914)
1 (25) 1 (25) 1 (25)
Unob
structed
Minimum
Operation
Clearance
36
(914)
36
(914)
36
(914)
36
(914)
Unob
structed
Note - Entire perimeter of unit base requires support when elevated above
mounting surface.
1
Service Clearance - Required for removal of serviceable parts.
Clearance to Combustibles - Required clearance to combustible material
(gas units).
Minimum Operation Clearance - Required clearance for proper unit operation.