Page 10
ELECTRICAL/ELECTRIC HEAT DATA
Model No. LHT156H4
1
Voltage - 60Hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 Ph
Compressor 1
(Non-Inverter)
Rated Load Amps
Locked Rotor Amps 55.3
Compressor 2
(Non-Inverter)
Rated Load Amps 22.4 7.7
Locked Rotor Amps 149 75 54
Outdoor Fan
2.4 1.3 1
Total 14.4
(2) 0.33 HP
Full Load Amps 2.4 1.3 1
Total 2
Service Outlet 115V GFI (amps) 15 15 20
Indoor Blower
Motor
Horsepower 3 5 3 5 3 5
Full Load Amps 3.9
2
Overcurrent
Protection (MOCP)
Unit Only 90 90 40 45 30 35
With (2) 0.33 HP
90 100 45 50 35 35
3
Minimum
Circuit
Ampacity (MCA)
Unit Only 71 77 35 29
With (2) 0.33 HP
37 40 31
ELECTRIC HEAT DATA
Electric Heat Voltage 208V 240V 208V 240V 480V 480V 600V 600V
2
Overcurrent
Protection (MOCP)
Unit+
Electric Heat
15 kW
4
110 125 125 125 45 50
30 kW
4
150 175 175 175 90 70 70
45 kW
4
200 225
4
200 225 110 110 90
60 kW
4
200 225 225 225 110 110 90 90
3
Minimum
Circuit
Ampacity (MCA)
Unit+
Electric Heat
15 kW 110 122 57 44 47
30 kW 149 155
45 kW 194 213 103 105
60 kW 215 202 222 107 110
2
Overcurrent
Protection (MOCP)
Unit+
Electric Heat
and (2) 0.33 HP
15 kW 125 125
4
125 150 70 50 50
30 kW 175 175 175 175 90 90 70 70
45 kW
4
200 225
4
200 225 110 110 90 90
60 kW 225 225
4
225 250 110 125 90 90
3
Minimum
Circuit
Ampacity (MCA)
Unit+
Electric Heat
and (2) 0.33 HP
15 kW 115 121 121 127 49
30 kW 154 172
45 kW 193 211 199 217 105
60 kW 201 220 207 110 112
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
2
HACR type breaker or fuse.
3
4
Factory installed circuit breaker not available.