EasyManuals Logo
Home>Lennox>Air Conditioner>M33A036S4-1P

Lennox M33A036S4-1P User Manual

Lennox M33A036S4-1P
258 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #165 background imageLoading...
Page #165 background image
Lennox Mini-Split Service Manual / Page 165
E8 Flow Chart
E8
Power off, then restart the unit 3 minutes
later. Is it still displaying the error code?
Yes
Shut off the power supply, and inspect all
components for damage. Rotate the fan
by hand, the Fan should offer little resis-
tance when manually spun. Wheel and
shaft should spin evenly and balanced.
Yes
Check all wiring connections.
Yes
Check main PCB, see index 1.
The unit operates normally.
No
Yes
Replace the fan motor.
Make necessary corrections
No
Correct faulty corrections.
No
Replace the main PCB.
No
No

Table of Contents

Other manuals for Lennox M33A036S4-1P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox M33A036S4-1P and is the answer not in the manual?

Lennox M33A036S4-1P Specifications

General IconGeneral
BrandLennox
ModelM33A036S4-1P
CategoryAir Conditioner
LanguageEnglish

Related product manuals