EasyManuals Logo
Home>Lennox>Air Conditioner>MCFA036S4-*P

Lennox MCFA036S4-*P User Manual

Lennox MCFA036S4-*P
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #142 background imageLoading...
Page #142 background image
142
Error Code: F6
Description: IndoorUnitEvaporatorOutletCoilTemperatureSensorFaulty
General Note: Ifthevoltageislowerthan0.06Vorhigherthan4.94V,theLEDwilldisplaytheerror.
Temperaturesensorerror
Checktheconnectionsbetweentempera-
turesensorandPCB.Aretheconnec-
tionsgood?
Yes
No
No
Correcttheconnections
Checktheresistancevalueofthesensor
via Appendix 1 and Appendix 2.
Yes
Replaceindoororout-
doorPCB.
Isitnormal?
No
Replacethesensor.

Table of Contents

Other manuals for Lennox MCFA036S4-*P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MCFA036S4-*P and is the answer not in the manual?

Lennox MCFA036S4-*P Specifications

General IconGeneral
BrandLennox
ModelMCFA036S4-*P
CategoryAir Conditioner
LanguageEnglish

Related product manuals