143
Error Code: P0
Description: IPMmoduleorIGBTovercurrentprotection.
General Note: WhenthevoltagesignalthatIPMsendstothecompressordrivechipisabnormal,thedisplayLEDwillshow“P6”andunit
willturnoff.
P6
Checkwhetherthevoltagerange
ofP-NonIPMmoduleisnormal?
277-356VDCfor18-30KBtu/h;277-
410VDCfor36KBtu/h
Checkwhethertheconnectingwiring
betweenmainboardandtheIPM
moduleisconnectedtightly.
Yes
Yes
No
Checkwhether
theinputpower
supply is cor-
rect?208-230V,
1PH,60Hz
No
No
Correcttheincom-
ingpowerproblem,
thencheckwhether
thesystemoperates
normally
Checkwhetherthe
powersupplyline
is connected cor-
rectlyandtightly.
No
Connect it correctly
andtightly,check
okornot?
Yes
No
Checkwhether
thelinesinE-
part box are con-
nectedtightly.
No
Connectittightly,
checkokornot?
NoYes
Checkwhetherthebridgerectiers
arenormal?Usethemultimeterto
measuretheresistancebetween
eachtwoterminals,checkwhether
thereistheconditionthatvalueof
resistance is 0.
Replacethe
bridgerectiers.
No
Yes
Checkwhetherthewiring
ofeachreactoriscorrect?
Replacethewiring
or reactor or replace
thePFCmodule
No
No
Connectittightly,
unit operates
correctly?
No
Yes
ReplacetheIPM
module,check
whetherthesystem
worksnormally.
No
Checkiftheoutdoor
fan runs properly
ortheoutdoorunit
ventilation is good.
ForACfanmodels,
checkwhethertheresis-
tanceofthefanmotor
is normal. If not, replace
thefanmotor.ForDC
fanmodels,refertothe
solution of fan speed
malfunction(E8).Find
outthecauseandrepair
it.
Yes
No
Replacethemainboard;
checkwhetherthesystem
operatesnormally?
No
Yes
Replacethecompressor,
checkwhetherthesystem
operatesnormally?
Problem Solved
Yes
Yes
Yes
Checkwhethertheconnectingwiring
tothecompressorisconnectedcor-
rectlyandtightly
Connectittightly,
checkokornot?
No
Yes