TABLE 3
1/4” QUICK CONNECT TERMINALS
120HUM Humidifier 120VAC
LINE 120VAC
XFMR Transformer 120VAC
CIRC Indoor blower 120VAC
EAC Indoor air quality accessory 120VAC
NEUTRALS Common 120VAC
HUM24 Humidifier 24VAC
3/16” QUICK CONNECT TERMINALS
COOL Cooling tap 24VAC
HEAT Heating tap 24VAC
FAN Continuous blower 24 VAC
PARK (no power) Park terminal for unused speed taps
FS Flame sense
24 COM Common 24VAC
TABLE 4
The integrated control is equipped with an LED light for troubleshooting. The diagnostic codes are listed below in table 4.
RED LED
Flash Code
2
Diagnostic Codes / Status of Furnace
Off No power to control or board fault detected
Heartbeat
1
Normal Operation - Idle, Continuous Fan, Cool
Continuous Rapid
Flash
Call For Heat / Burner Operation
1 Reverse Line Voltage Polarity
2 Improper Earth Ground
3 Burner failed to light, or lost flame during heat demand
4 Low Flame Signal - check flame sensor
5 Watchguard - burner failed to light, exceeded maximum number of retries or recycles.
6 Not Used
7
Primary or Secondary Limit Open or Watchguard Mode - Limit Switch Open longer than 3 min
utes
8 Rollout Switch Open
9 Pressure Switch failed to close or opened during heat demand
10 Watchguard - Pressure Switch opened 5 times during one heat demand
11 Pressure Switch stuck closed prior to activation of combustion air inducer
12 Flame Sensed without gas valve energized
13 Low Line Voltage
Notes
Note 1 A ”Heartbeat” is indicated by a ”Slow Flash” - 1 sec on 1 sec off, repeating
Note 2
Error codes are indicated by a ”Rapid Flash” - the LED flashes X times at 1/2 sec on 1/2 sec
off, remains off for 3 sec, then repeats
Note 3
Last 10 error codes are stored in memory including when power is shut off to the unit. - To recall,
press and release button, most recent will be displayed first, LED off for 3 sec, then next error
code is displayed, etc. To clear error codes, depress and hold button longer than 5 seconds.

Table of Contents

Other manuals for Lennox ML193UH090XE48C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox ML193UH090XE48C and is the answer not in the manual?

Lennox ML193UH090XE48C Specifications

General IconGeneral
BrandLennox
ModelML193UH090XE48C
CategoryFurnace
LanguageEnglish

Related product manuals