G- Proper Ground and Voltage
WARNING
Electric Shock Hazard. Can cause
injury or death. Unit must be properly
grounded in accordance with national
and local codes.
A poorly grounded furnace can contribute to premature ig
nitor failure. Use the following procedure to check for
ground and voltage to the integrated control.
1 - Measure the AC voltage between Line Neutral (spade
terminals) and “C” terminal (low voltage terminal
block) on the integrated control. See figure 56. A wide
variation in the voltage between Line Neutral and “C”
as a function of load indicates a poor or partial ground.
Compare the readings to the table below. If the read
ings exceed the maximum shown in table 1, make re
pairs before operating the furnace.
2 - In addition, measure the AC voltage from Line Hot to
Line Neutral (spade terminals) on the integrated con
trol. See figure 56. This voltage should be in the range
of 97 to 132 Vac
TABLE 20
Furnace Status
Measurement VAC
Expected Maximum
Power On Furnace Idle 0.3 2
CAI / Ignitor Energized 0.75 5
Indoor Blower Energized Less than 2 10
CHECK VOLTAGE BETWEEN LINE NEUTRAL
AND LOW VOLTAGE “C” TERMINAL
Red LED
Recall
Red LED
Recall
CHECK VOLTAGE BETWEEN LINE HOT
AND LINE NEUTRAL
FIGURE 56

Table of Contents

Other manuals for Lennox ML193UHE Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox ML193UHE Series and is the answer not in the manual?

Lennox ML193UHE Series Specifications

General IconGeneral
BrandLennox
ModelML193UHE Series
CategoryFurnace
LanguageEnglish

Related product manuals