147
Error Code: P2
Description: Compressortophightemperatureprotection(OLP)
General Note: Ifthesamplingvoltageisnot5V,theLEDwilldisplaytheP2errorcode.
P2
Checktheairowsystem
of indoor and outdoor units.
Doesaproblemexist?
No
Clearairowblockage.
Yes
Powerofftheunitandwait
10 minutes before restarting.
Yes
Checkcompressor
temperature.Isitwithin
acceptableparameters?
Checktheoverload
protector.Isitproperlywired?
No No
Yes
Measuretheresistance
betweenthetwoportsof
theOLP.Isitzero?
Yes
ReplacetheoutdoorcontrolPCB.
No
ReplacetheOLP.
Ensure a proper connection.
Yes
Error Code: P3
Description: Outdoorunitlowtemperaturelockout.
General Note: Theoutdoorunitwilllockoutifwheninheatingmode,whentheoutdoortemperatureislowerthan-13°F(-25°C)for1hour,
theindoorunitdisplayerrorcode.
Theoutdoorunitwillresumeoperationwheneither:
TheOUTDOORtemperatureishigherthan-7.6°F(-22°C)for10minutesandcompressorhasbeenstoppedfor1hour
or
Outdoortemperatureishigherthan23°F(-5°C)for10minutes

Table of Contents

Other manuals for Lennox MLA030S4M-*P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MLA030S4M-*P and is the answer not in the manual?

Lennox MLA030S4M-*P Specifications

General IconGeneral
BrandLennox
ModelMLA030S4M-*P
CategoryAir Conditioner
LanguageEnglish

Related product manuals