14
1.10. MPBMulti-ZoneSpecicationsOutdoorUnits(3-4Ton)
Nominal Size - Tons 3 4
Outdoor Unit Model No. MPB036S4M MPB048S4M
Number of Zones Up to 4 Up to 5
1
AHRI Ratings SystemType Ducted Non-Ducted Ducted Non-Ducted
Cooling-Btuh 36,000 36,000 48,000 48,000
HighTemperatureHeating-Btuh 36,000 36,000 50,000 48,000
LowTemperatureHeating-Btuh 22,800 24,600 33,000 29,600
SEER 17.9 22.5 17.6 22.4
EER 10.0 11.5 10.1 12.5
HSPF(RegionIV) 9.7 10.2 10.1 10.2
AHRIReferenceNumber 10062015 10062014 10062017 10062016
Energy Star No No No Yes
Ambient Temperature Range - °F Cooling –13 - 122 –13 - 122
Heating –13 - 86 –13 - 86
Sound Data (dBA) Cooling 62 64
Heating 62 64
Refrigerant Chargefurnished(R-410A) 6lbs.10oz. 10lbs.2oz.
Maximumlinelengthwithfurnishedcharge(perzone)-ft. 25 25
Additionalchargerequiredperft.-oz. 0.161 0.32
Compressor No.andType (1)Rotary (1)TwinRotary
Refrigerantoiltype VG74 VG74
Refrigerantoilcharge-oz. 33.8 47.3
Connections Liquid+Gas+Gaspipe(in.)are (4)1/4+(3)3/8+(1)1/2 (5)1/4+(3)3/8+(2)1/2
Max.lengthforallrooms-ft. 262 262
Max.lengthforoneindoorunit-ft. 115 115
Max.heightdifferencebetweenindoorandoutdoorunits-ft. 49 49
Max.heightdifferencebetweenindoorunits-ft. 33 33
Outdoor Fan (No.)Diameter-in. (1) 20 (2) 22
Totalairvolume-cfm 2130 4500
Motor rpm 150/200/250/300/400/500/600/750/
900/1000
150/200/250/300/400/500/600/700/
800/870
Outdoor Coil Numberofrows 2 2
Finsperinch 19 18
Fintype HydrophilicAluminum
Tubeoutsidediameter-in. 3/8 3/8
Tubetype RiedCopperTubing
Net face area - ft.
2
8.16 6.43(innercoil)/6.97(outercoil)
Application area - sq. ft. 515 - 755 690 - 1010
Design Pressure PSIG 550/340 550/340
Shipping Data Net/Shippingweight(lbs.) 157 / 168 224/255
ELECTRICAL DATA
Electrical Characteristics - 60 Hz - 1 Phase 208/230V 208/230V
2
MaximumOvercurrentProtection(amps) 45 50
3
Minimum circuit ampacity 30 35
CompressorRatedloadamps 22 21
Outdoor Fan Motor Ratedloadamps 1.3 (2) 0.39
Output-W 120 (2) 85
NOTE-PerAHRI,thecertiedratingsforsystemsarevalidforallcombinationsofindoorunitswiththespecicoutdoorunitslistedaboveandintheAHRIDirectoryof
CertiedEquipment.Pleasevisithttp://www.ahridirectory.orgforfurtherdetailsandlatestupdates.
1
RatingsareAHRIcertiedtoAHRIStandard1230-2010withAddendum2;
•CoolingRatings-80°Fdrybulb/67°Fwetbulbenteringindoorcoilairand95°Fdrybulb/75°Fwetbulboutdoorairtemperature.
•HighTemperatureHeatingRatings-70°Fdrybulb/60°Fwetbulbenteringindoorcoilairand47°Fdrybulb/43°Fwetbulboutdoorairtemperature.
•LowTemperatureHeatingRatings-70°Fdrybulb/60°Fwetbulbenteringindoorcoilairand17°Fdrybulb/15°Fwetbulboutdoorairtemperature.
NOTE-Extremesofoperatingrangeareplusandminus10%oflinevoltage.
2
HACRtypecircuitbreakerorfuse.
3
RefertoNationalorCanadianElectricalCodemanualtodeterminewire,fuseanddisconnectsizerequirements.
NOTE-Adaptorsarefurnishedforthegaspipeconnections:
036 - (3) 3/8 x 1/2 in. and (1) 1/2 x 3/8 in.
048-(3)3/8x1/2in.,(2)1/2x3/8in.,(2)1/4x3/8in.and(2)1/2x5/8in.