NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
RATINGS 7.5 TON
TS 6 to 20 Ton R−410A Air Conditioners / Page 18
AIR HANDLERS
COOLING CAPACITY − TSA090S4S with [TAA090S4D]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm L/s kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
63_F
(17_C)
2400 1135 88.5 25.9 5.78 .68 .82 .97 84.7 24.8 6.40 .69 .84 .99 80.6 23.6 7.13 .71 .87 1.00 76.1 22.3 7.95 .73 .90 1.00
3000 1415 92.7 27.2 5.86 .73 .90 1.00 88.5 25.9 6.48 .75 .93 1.00 84.0 24.6 7.20 .77 .96 1.00 79.1 23.2 8.02 .79 .99 1.00
3600 1700 95.8 28.1 5.91 .79 .97 1.00 91.3 26.8 6.54 .80 .99 1.00 87.0 25.5 7.26 .83 1.00 1.00 82.5 24.2 8.10 .86 1.00 1.00
67_F
(19_C)
2400 1135 93.5 27.4 5.87 .54 .65 .78 89.6 26.3 6.50 .54 .67 .80 85.3 25.0 7.22 .56 .69 .83 80.3 23.5 8.04 .57 .70 .86
3000 1415 97.5 28.6 5.95 .57 .70 .86 93.4 27.4 6.58 .58 .72 .89 88.6 26.0 7.29 .59 .74 .92 83.3 24.4 8.11 .60 .77 .95
3600 1700 100.7 29.5 6.01 .60 .76 .94 95.8 28.1 6.63 .60 .78 .97 91.1 26.7 7.34 .62 .81 .99 85.8 25.1 8.16 .64 .84 1.00
71_F
(22_C)
2400 1135 98.5 28.9 5.97 .41 .52 .63 94.2 27.6 6.59 .42 .53 .65 89.8 26.3 7.32 .42 .54 .66 84.8 24.9 8.15 .42 .56 .68
3000 1415 102.7 30.1 6.04 .43 .55 .69 98.2 28.8 6.68 .43 .57 .70 93.3 27.3 7.39 .43 .58 .72 87.8 25.7 8.20 .44 .58 .74
3600 1700 105.8 31.0 6.10 .44 .59 .74 100.7 29.5 6.72 .44 .59 .75 95.6 28.0 7.44 .45 .61 .78 90.2 26.4 8.26 .45 .63 .81
COOLING CAPACITY − TSA090S4S with [TAA120S4D]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm L/s kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
63_F
(17_C)
2400 1135 89.7 26.3 5.80 .68 .82 .97 85.6 25.1 6.43 .69 .84 .99 81.4 23.9 7.14 .70 .87 1.00 76.8 22.5 7.97 .73 .90 1.00
3000 1415 93.9 27.5 5.88 .73 .91 1.00 89.5 26.2 6.50 .75 .94 1.00 85.1 24.9 7.22 .77 .97 1.00 80.1 23.5 8.04 .79 1.00 1.00
3600 1700 97.0 28.4 5.94 .78 .98 1.00 92.7 27.2 6.56 .81 1.00 1.00 88.7 26.0 7.30 .83 1.00 1.00 84.1 24.6 8.13 .87 1.00 1.00
67_F
(19_C)
2400 1135 94.9 27.8 5.89 .54 .65 .78 90.8 26.6 6.52 .55 .67 .80 86.0 25.2 7.24 .55 .68 .83 81.5 23.9 8.07 .56 .71 .86
3000 1415 99.3 29.1 5.98 .57 .71 .87 94.8 27.8 6.60 .58 .72 .90 89.8 26.3 7.32 .59 .75 .93 84.4 24.7 8.13 .60 .77 .96
3600 1700 102.1 29.9 6.03 .60 .76 .95 97.3 28.5 6.66 .61 .78 .98 92.3 27.1 7.37 .62 .81 1.00 87.0 25.5 8.19 .63 .85 1.00
71_F
(22_C)
2400 1135 100.0 29.3 5.99 .41 .52 .63 95.6 28.0 6.63 .42 .53 .65 90.9 26.6 7.34 .42 .54 .67 85.8 25.1 8.17 .42 .55 .68
3000 1415 104.9 30.7 6.09 .42 .56 .69 99.8 29.2 6.71 .43 .57 .70 94.8 27.8 7.42 .43 .58 .72 89.1 26.1 8.24 .43 .59 .74
3600 1700 107.6 31.5 6.15 .44 .59 .73 102.3 30.0 6.77 .44 .59 .76 97.4 28.5 7.48 .45 .62 .79 91.5 26.8 8.29 .46 .63 .82
COOLING CAPACITY − (2) TSA090S4S (FIRST STAGE) with [TAA180S4D]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
65_F (18_C) 75_F (24_C) 85_F (29_C) 95_F (35_C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm L/s kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
63_F
(17_C)
4800 2265 91.2 26.7 4.63 .67 .79 .93 88.1 25.8 5.13 .67 .81 .95 84.6 24.8 5.69 .69 .83 .97 80.8 23.7 6.32 .70 .85 .99
6000 2830 95.6 28.0 4.70 .71 .86 1.00 92.2 27.0 5.20 .72 .88 1.00 88.4 25.9 5.76 .73 .90 1.00 84.4 24.7 6.39 .75 .93 1.00
7200 3400 98.6 28.9 4.76 .75 .93 1.00 95.1 27.9 5.25 .76 .95 1.00 91.2 26.7 5.81 .78 .97 1.00 87.1 25.5 6.44 .80 .99 1.00
67_F
(19_C)
4800 2265 95.9 28.1 4.71 .53 .64 .76 92.7 27.2 5.21 .54 .65 .77 89.1 26.1 5.77 .54 .66 .79 85.2 25.0 6.40 .55 .67 .81
6000 2830 100.5 29.5 4.79 .56 .68 .83 96.9 28.4 5.29 .56 .69 .85 93.1 27.3 5.84 .57 .71 .87 88.7 26.0 6.47 .58 .72 .89
7200 3400 103.7 30.4 4.85 .58 .72 .89 99.9 29.3 5.34 .59 .74 .91 95.9 28.1 5.90 .60 .76 .94 91.3 26.8 6.52 .61 .78 .96
71_F
(22_C)
4800 2265 100.5 29.5 4.79 .42 .52 .62 97.2 28.5 5.29 .42 .52 .63 93.4 27.4 5.85 .42 .53 .64 89.3 26.2 6.48 .42 .54 .65
6000 2830 105.2 30.8 4.88 .42 .54 .66 101.6 29.8 5.37 .42 .55 .67 97.5 28.6 5.93 .42 .56 .69 93.1 27.3 6.55 .43 .57 .70
7200 3400 108.6 31.8 4.94 .43 .57 .70 104.6 30.7 5.43 .43 .58 .72 100.4 29.4 5.98 .44 .59 .73 95.9 28.1 6.61 .45 .60 .76
COOLING CAPACITY − (2) TSA090S4S (SECOND STAGE) with [TAA180S4D]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm L/s kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
63_F
(17_C)
4800 2265 169.3 49.6 11.38 .69 .83 .97 161.7 47.4 12.63 .70 .85 .99 154.1 45.2 14.09 .71 .87 1.00 145.2 42.6 15.75 .73 .90 1.00
6000 2830 176.9 51.8 11.51 .73 .90 1.00 168.8 49.5 12.77 .75 .93 1.00 160.4 47.0 14.21 .77 .95 1.00 151.1 44.3 15.84 .80 .99 1.00
7200 3400 182.4 53.5 11.62 .78 .97 1.00 174.3 51.1 12.87 .80 .99 1.00 165.3 48.4 14.31 .83 1.00 1.00 157.0 46.0 15.97 .86 1.00 1.00
67_F
(19_C)
4800 2265 178.2 52.2 11.54 .54 .66 .79 170.4 49.9 12.81 .55 .67 .81 161.9 47.4 14.23 .56 .69 .83 152.9 44.8 15.90 .57 .71 .87
6000 2830 186.1 54.5 11.68 .57 .71 .87 177.4 52.0 12.93 .58 .72 .89 168.8 49.5 14.37 .59 .74 .92 158.9 46.6 16.03 .60 .77 .95
7200 3400 191.7 56.2 11.79 .60 .76 .94 182.5 53.5 13.03 .61 .78 .96 173.3 50.8 14.47 .62 .81 .99 163.1 47.8 16.11 .64 .84 1.00
71_F
(22_C)
4800 2265 186.7 54.7 11.70 .42 .53 .64 178.7 52.4 12.96 .42 .54 .65 170.0 49.8 14.40 .42 .55 .67 160.6 47.1 16.04 .43 .56 .69
6000 2830 194.9 57.1 11.86 .42 .56 .69 186.2 54.6 13.11 .43 .57 .70 176.9 51.8 14.55 .44 .58 .72 167.1 49.0 16.19 .44 .59 .75
7200 3400 200.8 58.8 11.97 .44 .59 .73 191.8 56.2 13.22 .45 .60 .76 182.1 53.4 14.64 .45 .61 .78 171.3 50.2 16.27 .45 .63 .82