NOTES: For Temperatures and Capacities not shown in tables, see bulletin ā Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
RATINGS 7.5 TON
TS 6 to 20 Ton Rā410A Air Conditioners / Page 19
UPāFLOW INDOOR COIL
COOLING CAPACITY ā TSA090S4S with [(2) CX34ā49Cā6F]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm L/s kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
63_F
(17_C)
2400 1135 87.5 25.6 5.76 .67 .81 .95 83.8 24.6 6.39 .69 .83 .97 79.7 23.4 7.11 .70 .85 1.00 75.3 22.1 7.94 .72 .88 1.00
3000 1415 91.7 26.9 5.84 .71 .88 1.00 87.7 25.7 6.46 .73 .90 1.00 83.4 24.4 7.19 .75 .93 1.00 78.7 23.1 8.01 .78 .97 1.00
3600 1700 95.1 27.9 5.90 .76 .95 1.00 90.8 26.6 6.53 .78 .98 1.00 86.3 25.3 7.24 .81 1.00 1.00 81.9 24.0 8.08 .84 1.00 1.00
67_F
(19_C)
2400 1135 91.7 26.9 5.83 .54 .65 .77 87.8 25.7 6.47 .55 .66 .79 83.7 24.5 7.19 .55 .68 .81 79.2 23.2 8.02 .56 .69 .84
3000 1415 96.3 28.2 5.92 .56 .69 .84 92.0 27.0 6.55 .57 .71 .87 87.6 25.7 7.27 .58 .73 .90 82.8 24.3 8.09 .60 .75 .93
3600 1700 99.6 29.2 5.98 .59 .74 .91 95.1 27.9 6.61 .60 .76 .94 90.5 26.5 7.32 .61 .78 .97 85.3 25.0 8.15 .62 .81 1.00
71_F
(22_C)
2400 1135 96.4 28.3 5.92 .42 .53 .63 92.1 27.0 6.55 .42 .53 .64 87.9 25.8 7.28 .42 .55 .65 83.0 24.3 8.10 .42 .55 .67
3000 1415 100.6 29.5 6.01 .43 .55 .67 96.1 28.2 6.63 .43 .56 .69 91.6 26.8 7.35 .44 .57 .70 86.5 25.4 8.18 .44 .59 .73
3600 1700 104.1 30.5 6.08 .44 .58 .71 99.5 29.2 6.71 .44 .59 .73 94.7 27.8 7.42 .45 .60 .76 89.2 26.1 8.23 .45 .62 .79
DOWNāFLOW INDOOR COILS
COOLING CAPACITY ā TSA090S4S with [(2) CR33ā50/60CāF]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm L/s kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
63_F
(17_C)
2400 1135 86.1 25.2 5.73 .68 .81 .96 82.2 24.1 6.36 .69 .83 .98 78.3 22.9 7.08 .70 .86 1.00 73.8 21.6 7.91 .72 .89 1.00
3000 1415 89.9 26.3 5.80 .72 .88 1.00 85.9 25.2 6.43 .74 .91 1.00 81.6 23.9 7.15 .76 .94 1.00 76.8 22.5 7.97 .78 .97 1.00
3600 1700 92.7 27.2 5.85 .77 .95 1.00 88.5 25.9 6.48 .79 .98 1.00 84.3 24.7 7.20 .81 .99 1.00 80.1 23.5 8.04 .84 1.00 1.00
67_F
(19_C)
2400 1135 90.7 26.6 5.82 .54 .66 .78 86.7 25.4 6.45 .55 .67 .80 82.6 24.2 7.17 .56 .68 .82 78.0 22.9 7.99 .57 .70 .85
3000 1415 94.8 27.8 5.89 .57 .70 .85 90.6 26.6 6.52 .58 .71 .87 86.0 25.2 7.24 .59 .73 .90 81.2 23.8 8.07 .60 .76 .94
3600 1700 97.8 28.7 5.95 .59 .74 .92 93.4 27.4 6.58 .60 .76 .95 88.5 25.9 7.29 .61 .79 .97 83.3 24.4 8.11 .63 .82 1.00
71_F
(22_C)
2400 1135 95.2 27.9 5.90 .41 .53 .64 91.1 26.7 6.53 .42 .54 .65 86.8 25.4 7.26 .41 .55 .66 82.1 24.1 8.09 .42 .55 .68
3000 1415 99.5 29.2 5.98 .42 .56 .68 95.2 27.9 6.61 .43 .57 .69 90.5 26.5 7.33 .43 .58 .71 85.5 25.1 8.16 .44 .59 .73
3600 1700 102.8 30.1 6.05 .44 .58 .72 98.0 28.7 6.67 .44 .59 .74 93.2 27.3 7.39 .45 .61 .76 87.7 25.7 8.19 .45 .62 .79
HORIZONTAL INDOOR COILS
COOLING CAPACITY ā TSA090S4S with [(2) CH33ā49Cā2F]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm L/s kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
63_F
(17_C)
2400 1135 87.6 25.7 5.76 .67 .81 .95 83.7 24.5 6.39 .68 .83 .98 79.7 23.4 7.11 .70 .85 1.00 75.1 22.0 7.93 .71 .88 1.00
3000 1415 91.7 26.9 5.83 .71 .88 1.00 87.6 25.7 6.46 .73 .91 1.00 83.4 24.4 7.19 .75 .93 1.00 78.5 23.0 8.01 .78 .97 1.00
3600 1700 94.9 27.8 5.90 .76 .95 1.00 90.6 26.6 6.52 .78 .98 1.00 85.7 25.1 7.23 .80 1.00 1.00 81.6 23.9 8.07 .84 1.00 1.00
67_F
(19_C)
2400 1135 92.4 27.1 5.85 .54 .65 .77 88.4 25.9 6.48 .54 .66 .79 84.1 24.6 7.20 .55 .67 .81 79.6 23.3 8.03 .56 .69 .84
3000 1415 96.9 28.4 5.93 .56 .69 .84 92.5 27.1 6.56 .57 .71 .87 87.9 25.8 7.28 .58 .73 .90 82.8 24.3 8.10 .59 .75 .93
3600 1700 99.9 29.3 5.99 .59 .74 .92 95.4 28.0 6.62 .60 .76 .94 90.4 26.5 7.33 .60 .78 .97 85.0 24.9 8.14 .62 .81 1.00
71_F
(22_C)
2400 1135 97.0 28.4 5.94 .42 .52 .63 92.9 27.2 6.57 .42 .53 .64 88.4 25.9 7.29 .42 .54 .65 83.7 24.5 8.12 .42 .55 .67
3000 1415 101.7 29.8 6.02 .42 .55 .67 97.2 28.5 6.66 .43 .56 .69 92.5 27.1 7.38 .43 .57 .70 87.2 25.6 8.20 .44 .58 .73
3600 1700 105.0 30.8 6.09 .44 .58 .71 100.3 29.4 6.72 .44 .59 .74 95.2 27.9 7.43 .45 .60 .76 89.6 26.3 8.24 .45 .61 .79