Page 2
Specifications and Electrical Data
ONE PHASE
General
Data
Model No. TSA024S4 TSA030S4 TSA036S4 TSA048S4 TSA060S4
Nominal kW (tonnage) 7.0 (2) 8.8 (2.5) 10.5 (3) 14.1 (4) 17.6 (5)
Connections
(sweat)
Liquid line o.d. − in. 3/8 3/8 3/8 3/8 3/8
Suction line o.d. − in. 3/4 3/4 7/8 7/8 1−1/8
1
Refrigerant (R−410A) furnished
1.98 kg
(4 lbs. 6 oz.)
1.93 kg
(4 lbs. 4 oz.)
2.89 kg
(6 lbs. 6 oz.)
3.40 kg
(7 lbs. 8 oz.)
4.54 kg
(10 lbs.)
Outdoor
Coil
Net face area
m
2
(sq. ft.)
Outer coil 1.05 (11.33) 1.23 (13.22) 1.52 (16.33) 1.95 (21.0) 1.73 (18.67)
Inner coil − − − − − − − − − − − − 1.67 (17.96)
Tube diameter − in. 5/16 5/16 5/16 5/16 5/16
Number of rows 1 1 1 1 2
Fins per meter (per inch) 1024 (26) 1024 (26) 1024 (26) 1024 (26) 866 (22)
Outdoor
Fan
Diameter − mm. 457 (18) 457 (18) 559 (24) 559 (24) 559 (24)
Number of blades 3 4 4 4 4
Motor W (hp) 75 (1/10) 150 (1/5) 185 (1/4) 185 (1/4) 185 (1/4)
L/s (cfm) 924 (1958) 944 (2000) 1377 (2917) 1443 (3058) 1416 (3000)
Rev/min 842 908 688 696 692
Watts 138 154 250 246 238
Shipping Data − kg (lb.) 1 package 56 (123) 60 (133) 81 (178) 88 (194) 99 (218)
Electrical Data
Line voltage data − 50 hz − 1 phase 220 / 240V 220 / 240V 220 / 240V 220 / 240V 220 / 240V
2
Maximum overcurrent protection (amps) 25 25 35 35 45
3
Minimum circuit ampacity 14.3 16.9 21.7 21.6 26.9
Compressor Rated load amps 10.9 12.2 16.0 15.9 20.2
Locked rotor amps 60.0 67.0 87.0 98.0 128.0
Condenser
Fan Motor
Full load amps 0.7 1.1 1.7 1.7 1.7
Locked rotor amps 1.4 2.0 3.1 3.1 3.1
NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Refrigerant charge sufficient for 4.6 m (15 ft.) length of refrigerant lines.
2
Heating Air Conditioning and Refrigeration type circuit breaker or fuse.
3
Refer to local codes to determine wire, fuse and disconnect size requirements.