Page 2
SPECIFICATIONS −1 units and 030 through 060 −2 units
General
Model No. XC14−018 XC14−024 XC14−030 XC14−036 XC14−042 XC14−048 XC14−060
Data
Nominal Tonnage 1.5
2 2.5 3 3.5 4 5
Connections
Liquid line o.d. − in. 3/8 3/8 3/8 3/8 3/8 3/8 3/8
(sweat)
Suction line o.d. − in. 3/4
3/4 3/4 7/8 7/8 7/8 1-1/8
1
Refrigerant (R-410A) furnished 6 lbs. 12 oz. 7 lbs. 10 oz. 8 lbs. 0 oz. 8 lbs. 9 oz. 8 lbs. 10 oz. 10 lbs. 0 oz. 12 lbs. 0 oz.
Outdoor
Net face area -
Outer coil 13.22 13.22 16.33 16.33 16.33 21.00 22.00
Coil sq. ft.
Inner coil 12.60
12.60 15.71 15.71 15.71 20.25 21.33
Tube diameter − in. 5/16 5/16 5/16 5/16 5/16 5/16 5/16
Number of rows 2 2 2 2 2 2 2
Fins per inch 22 22 22 22 22 22 22
Outdoor
Diameter − in. 18 18 22 22 22 22 26
Fan
Number of blades 4
4 4 4 4 4 4
Motor hp 1/5 1/5 1/6 1/6 1/4 1/4 1/3
Cfm 2400 2400 2900 2900 3500 3600 4400
Rpm 1100 1100 825 825 825 825 825
Watts 200 200 220 220 310 310 310
Shipping Data − lbs. 1 package 146 148 169 172 198 221 238
ELECTRICAL DATA
Line voltage data − 60 hz − 1ph 208/230V 208/230V 208/230V 208/230V 208/230V 208/230V 208/230V
2
Maximum overcurrent protection (amps) 20 30 30 30 40 50 60
3
Minimum circuit ampacity 12.3 17.9 17.2 18.7 24.1 29.0 34.8
Compressor
Rated load amps
9.0 13.4 12.9 14.1 17.9 21.8 26.4
Power factor
.96
.97 .98 .98 .94 .95 .98
Locked rotor amps
48
58 64 77 112 117 134
Condenser
Full load amps
1.0 1.0 1.1 1.1 1.7 1.7 1.8
Fan Motor
Locked rotor amps
1.9
1.9 2.1 2.1 3.1 3.1 2.9
OPTIONAL ACCESSORIES − must be ordered extra
Compressor Crankcase Heat-
93M05
er
93M06
Factory Factory
Compressor Hard Start Kit
10J42
88M91
Compressor Low Ambient Cut−Off 45F08
Compressor Time−Off Control 47J27
Freezestat
3/8 in. tubing 93G35
5/8 in. tubing 50A93
Indoor Blower Off Delay Relay 58M81
Loss of Charge Switch Kit 84M23
Low Ambient Kit 34M72
Refrigerant
Line Sets
L15−41−20, L15−41−30,
L15−41−40, L15−41−50
L15−65−30, L15−65−40,
L15−65−50
Field Fabricate
NOTE Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Refrigerant charge sufficient for 15 ft. length of refrigerant lines.
2
HACR type circuit breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.