Troubleshooting and fault elimination
8-6 UOMu_^MVMO
Function You can select whether the active fault is to be reset automatically or manually.
Auto-Trip reset does not reset all faults automatically.
Activation C170 = -0-:
D Manual TRIP-reset
D STP key
D LOW signal at terminal 28
C170 = -1-:
Auto-Trip reset resets the following fault messages after the time set under C171:
- OC3 (overload during acceleration)
- OC4 (overload during deceleration)
- OC5 (overload)
-OC6(I
¡ t s witch-off)
- OH (overtemperature)
- OUE (overvoltage in DC bus)
Important Mains switching always resets TRIP.
With more than 8 auto-trip resets within 10 minutes, the controller s ets TRIP and
indicates rST (numerator exceeded).
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze 8200 series and is the answer not in the manual?

Lenze 8200 series Specifications

General IconGeneral
CategoryInverter
Output voltage range0 V to input voltage
Control modesvector control
Communication interfacesRS485, CANopen, Profibus, Ethernet
Protection featuresOvercurrent, overvoltage, undervoltage, short circuit, overtemperature
Relative humidity95 % (non-condensing)
Protection classIP20

Related product manuals