Lenze · E94AYCET communication module (EtherCAT®) · Communication Manual · DMS 10.2 EN · 11/2018 · TD06 135
14 Parameter reference
14.3 Parameters of the communication module for slot MXI2
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14899
C14900
C14901
C14902
Parameter | Name:
C14899 | Station alias
Data type: UNSIGNED_16
Index: 9676 = 0x25CC
This code serves to set a station alias.
In order to use a station alias, you must select a value > "0".
The station alias must only be set if the device is part of a "hot connect" group or
integrated in the modular
machine configuration of Lenze.
The station alias must be unambiguous and must only be assigned once within the EtherCAT network.
Use the same station alias in the EtherCAT master and in the slave.
Address allocation
( 35)
Setting range (min. value | unit | max. value) Lenze setting
0 32767 0
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14900 | Firmware: Product type
Data type: VISIBLE_STRING
Index: 9675 = 0x25CB
The code contains a string with a length of 8 bytes.
The following identification code is output: "E94AFCET".
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14901 | Firmware compilation date
Data type: VISIBLE_STRING
Index: 9674 = 0x25CA
The code contains a string with a length of 20 bytes. The creation date ("MM DD YYYY") and the time ("hh:mm:ss")
of the software are output here.
Example: "Mar 21 2005 12:31:21"
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14902 | Firmware version
Data type: VISIBLE_STRING
Index: 9673 = 0x25C9
The code contains a string with a length of 11 bytes. The firmware version is output here.
Example: "02.00.00.36"
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT