Electrical installaon
Important notes
NOTE
When installing the devices into a control cabinet with a spaal distance, separate the devices that generate
high voltage and electromagnec interference from low-voltage devices such as the IoT Gateway x500.
NOTE
Unstable LAN connecon due to wrong cable types.
The LAN connecon might be interrupted.
Only use cables of CAT5-S/FTP type or beer.
Mains connecon
SELV/PELV
(LPS)
L1
N
PE
L1
N
0V
+24
~ =
F
(max. 20 A)
PE
IoT Gateway x500
GND
24E
DI1
PE
Terminal data
Mains connecon
Digital control signal
GND
24E
DI1
+
-
+
-
12-24 V DC
PE
Connecon X50
Connecon type Connector
Weidmüller BL
5.08/04/180 SN BK BX
Min. cable cross-secon mm² 0.75 (AWG18)
Max. cable cross-secon mm² 1.5 (AWG14)
Stripping length mm 7
Tightening torque Nm 0.4
Digital input DI1
Voltage range 0 - 29 V DC
Current range (ON) 2 - 5 mA
Voltage range (LOW) 0 - 3 V DC
Voltage range (HIGH) 7 - 29 V DC
By default, the digital input is not congured and does not need to be wired. The digital input
provides the opportunity to locally acvate/deacvate the VPN connecon of the
IoT Gateway x500 (ON/OFF).
Electrical installaon

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze IoT Gateways x510 LAN and is the answer not in the manual?

Lenze IoT Gateways x510 LAN Specifications

General IconGeneral
BrandLenze
ModelIoT Gateways x510 LAN
CategoryGateway
LanguageEnglish

Related product manuals