Electrical installaon
Important notes
NOTE
When installing the devices into a control cabinet with a spaal distance, separate the devices that generate
high voltage and electromagnec interference from low-voltage devices such as the IoT Gateway x500.
NOTE
Unstable LAN connecon due to wrong cable types.
The LAN connecon might be interrupted.
► Only use cables of CAT5-S/FTP type or beer.
Mains connecon
SELV/PELV
(LPS)
L1
N
PE
L1
N
0V
+24
~ =
F
(max. 20 A)
PE
IoT Gateway x500
GND
24E
DI1
PE
Terminal data
Mains connecon
Digital control signal
GND
24E
DI1
+
-
+
-
12-24 V DC
PE
Connecon X50
Connecon type Connector
Weidmüller BL
5.08/04/180 SN BK BX
Min. cable cross-secon mm² 0.75 (AWG18)
Max. cable cross-secon mm² 1.5 (AWG14)
Stripping length mm 7
Tightening torque Nm 0.4
Digital input DI1
Voltage range 0 - 29 V DC
Current range (ON) 2 - 5 mA
Voltage range (LOW) 0 - 3 V DC
Voltage range (HIGH) 7 - 29 V DC
By default, the digital input is not congured and does not need to be wired. The digital input
provides the opportunity to locally acvate/deacvate the VPN connecon of the
IoT Gateway x500 (ON/OFF).
Electrical installaon