Safety instructions
Residual hazards
2
70
EDK94SH366 ZH/EN 3.1
2.2 Residual hazards
Protection of persons
ƒ Before starting work on the controller, check that the power terminals are
deenergised
because the power terminals U, V, W, +UG, −UG, Rb1 and Rb2 carry hazardous
voltages for up to 20 minutes after power−off.
because the power terminals L1, L2, L3; U, V, W, +UG, −UG, Rb1 and Rb2 carry
hazardous voltages when the motor is stopped.
Device protection
ƒ Plug on or pull off all pluggable terminals only in deenergised condition!
ƒ Cyclically switching on and off of the mains voltage can overload and destroy the
input current limitation of the controller:
In the case of cyclic mains switching for a longer time period, allow at least one
minute between two switch−on actions!
Motor protection
ƒ Depending on the controller settings, the connected motor can be overheated by:
For instance, longer DC−braking operations.
Longer operation of self−ventilated motors at low speed.
Protection of the machine/system
ƒ Drives can reach dangerous overspeeds (e.g. setting of high output frequencies in
connection with motors and machines unsuitable for such conditions):
The controllers do not offer any protection against such operating conditions. Use
additional components for this purpose.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze L-force Drives E94ASHE Series and is the answer not in the manual?

Lenze L-force Drives E94ASHE Series Specifications

General IconGeneral
BrandLenze
ModelL-force Drives E94ASHE Series
CategoryServo Drives
LanguageEnglish

Related product manuals